DISTRIBUTION TRANSFORMERS HARMONICS AND DC EFFECTS BASIC INFORMATION
What Are The Harmonics And DC Effects Of Distribution Transformers?
Harmonics and DC Effects
Rectifier and discharge-lighting loads cause currents to flow in the distribution transformer that are not pure power-frequency sine waves. Using Fourier analysis, distorted load currents can be resolved into components that are integer multiples of the power frequency and thus are referred to as harmonics.
Distorted load currents are expected to be high in the 3rd, 5th, 7th, and sometimes the 11th and 13th harmonics, depending on the character of the load.
Odd-Ordered Harmonics
Load currents that contain the odd-numbered harmonics will increase both the eddy losses and other stray losses within a transformer. If the harmonics are substantial, then the transformer must be derated to prevent localized and general overheating.
ANSI standards suggest that any transformer with load current containing more than 5% total harmonic \ distortion should be loaded according to the appropriate ANSI guide (IEEE, 1998).
Even-Ordered Harmonics
Analysis of most harmonic currents will show very low amounts of even harmonics (2nd, 4th, 6th, etc.) Components that are even multiples of the fundamental frequency generally cause the waveform to be nonsymmetrical about the zero-current axis.
The current therefore has a zeroth harmonic or dc-offset component. The cause of a dc offset is usually found to be half-wave rectification due to a defective rectifier or other component.
The effect of a significant dc current offset is to drive the transformer core into saturation on alternate half-cycles. When the core saturates, exciting current can be extremely high, which can then burn out the primary winding in a very short time.
Transformers that are experiencing dc-offset problems are usually noticed because of objectionably loud noise coming from the core structure. Industry standards are not clear regarding the limits of dc offset on a transformer.
A recommended value is a dc current no larger than the normal exciting current, which is usually 1% or less of a winding’s rated current (Galloway, 1993).
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
February
(28)
- POWER TRANSFORMER PROTECTIVE MAINTENANCE BASICS AN...
- TRANSFORMER OIL CONTAINMENT BASICS AND TUTORIALS
- DISTRIBUTION TRANSFORMERS HARMONICS AND DC EFFECTS...
- CAN 60 HZ TRANSFORMERS BE OPERATED AT 50 HZ? BASIC...
- TRANSFORMER PARTS STORAGE GOOD PRACTICE BASICS AND...
- TRANSFORMER MINERAL INSULATING OIL HEALTH AND ENVI...
- TRANSFORMER OILS TESTING OF NEW OIL PROPERTIES BAS...
- INRUSH CURRENT CONSIDERATION FOR TRANSFORMERS BASI...
- POWER TRANSFORMER TEMPERATURE RISE TEST AT LOAD BE...
- TRANSFORMER BUSHINGS BASICS AND TUTORIALS
- TRANSFORMER LOSSES DEFINITION BASIC AND TUTORIALS
- MATCHING TRANSFORMERS FOR PARALLEL AND BANK OPERAT...
- EFFECTS OF SHORT CIRCUITS ON TRANSFORMERS BASICS A...
- EQUIVALENT CIRCUIT OF A THREEWINDING TRANSFORMER B...
- THREE WINDING TRANSFORMER BASIC INFORMATION What I...
- ADVANTAGES AND DISADVANTAGES OF THE AUTOTRANSFORME...
- POOR POWER QUALITY (PQ) EFFECTS ON TRANSFORMERS BA...
- BUCHHOLZ RELAY OR POWER TRANSFORMER BASICS AND TUT...
- THE SCOTT TRANSFORMER CONNECTION BASIC AND TUTORIALS
- TRANSFORMING THREE-PHASE VOLTAGES INTO TWO-PHASE V...
- PAD MOUNTED TRANSFORMERS SINGLE PHASE BASIC AND TU...
- POWER TRANSFORMER IMPACT RECORDER BASICS AND TUTOR...
- SINGLE PHASE TRANSFORMER POLARITY BASICS AND TUTOR...
- FERRORESONANCE AND DISTRIBUTION TRANSFORMER CONTRI...
- ZIGZAG CONNECTION OF TRANSFORMER BASICS AND TUTORIALS
- POWER TRANSFORMERS INSULATING LIQUIDS BASICS AND T...
- DIFFERENCE BETWEEN DRY TYPE AND LIQUID FILLED TRAN...
- TRANSFORMER FAILURE MODE BASICS AND TUTORIALS
-
▼
February
(28)
How do i check harmonics in my three winding 1260 kva 34.5/380 volt 3 phase power transformer. It is connected to a solar inverter.
ReplyDelete