POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Showing posts with label Connection. Show all posts
Showing posts with label Connection. Show all posts
THREE-PHASE CONNECTIONS OF SINGLE-PHASE TRANSFORMERS BASIC INFORMATION AND TUTORIALS
Single-phase transformers can be connected to form three-phase transformer banks for stepping voltages up or down in three-phase systems. Four common configurations for connecting transformers in three-phase systems are delta–delta, wye–wye, wye–delta, and delta–wye.
The first three are shown in Fig. 3-9. The delta–wye is not shown because it is simply the reverse of the wye–delta connection.
Delta–delta connection
The delta–delta connection, shown in Fig. 3-9a, is widely used for moderate voltages. This connection has the advantage of remaining operational in what is known as the open delta or V connection if one transformer is damaged or taken out of service, leaving the remaining two functional.
If it is operated this way, the bank still delivers three-phase currents and voltages in their correct phase relationships. However, the capacity of the bank is reduced to 57.7 percent of the value obtained with all three transformers in service.
Wye–wye connection
In the wye–wye connection, shown in Fig. 3-9b, only 57.7 percent (or 1/1.73) of the line voltage is applied to each winding, but full line current flows in each transformer winding. The drawback to this connection is that power circuits supplied from a wye–wye bank generate serious electromagnetic interference, which could interrupt nearby communications circuits.
Because of this and other disadvantages, the wye–wye connection is seldom used. However, the wye–wye connection can be used to interconnect two delta systems and provide suitable neutrals for grounding both of them.
Delta–wye and wye–delta connections
The delta–wye connection (not shown) is suitable for stepping up voltages because the voltage is increased by the transformer ratio multiplied by a factor of 1.73. Similarly, the wye–delta connection, shown in Fig. 3-9c, is used for stepping down voltages.
The high-voltage windings of most transformers operating at more than 100 kV are wye-connected. To match the polarities correctly in a wye connection, the H and X markings must be connected symmetrically.
In other words, if an H1 or X1 terminal is connected to the neutral, then all of the H1 or X1 terminals must be connected to the neutral and the remaining H2 or X2 terminals must be brought out as the line connections, as shown in Fig. 3-9b.
By contrast, in a delta connection, H1 must always be connected to H2 and X1 to X2, and the line connections must be made at these junctions, as shown in Fig. 3-9a.
When a large number of single-phase loads are to be served from a three-phase transformer bank, the wye connected low-voltage winding is recommended because the single-phase loads can be balanced evenly on all phases.
THREE (3) PHASE TO THREE (3) PHASE CONVERSION BASIC INFORMATION AND TUTORIALS
The delta-delta, the delta-Y, and the Y-Y connections are the most generally used; they are illustrated in figure below. The Y-delta and delta-delta connections may be used as step-up transformers for moderate voltages.
![]() | ||
| Standard 3-phase/3-phase transformer | systems. |
Delta connections are not the best for transmission at very high voltage; they may, however, be associated at some point with other connections that provide means for properly grounding the high voltage system; but it is better, on the whole, to avoid mixed systems of connections. The delta-Y step-up and Y-delta step-down connections are without question the best for high voltage transmission systems.
They are economical in cost, and provide a stable neutral whereby the high-voltage system may be directly grounded or grounded through resistance of such value as to damp the system critically and prevent the possibility of oscillation.
The Y-Y connection (or Y-connected autotransformer) may be used to interconnect two delta systems and provide suitable neutrals for grounding both of them. A Y-connected autotransformer may be used to interconnect two Y systems which already have neutral grounds, for reasons of economy.
In either case, a delta-connected tertiary winding is frequently provided for one or more of the following purposes. In stabilization of the neutral, if a Y-connected transformer (or autotransformer) with a delta connected tertiary is connected to an ungrounded delta system (or poorly grounded Y system), stability of the system neutral is increased.
That is, a single-phase short-circuit to ground on the transmission line will cause less drop in voltage on the short-circuited phase and less rise in voltage on the other two phases. A 3-phase three-leg Y-connected transformer without delta tertiary furnishes very little stabilization of the neutral, and the delta tertiary is generally needed.
Other Y connections offer no stabilization of the neutral without a delta tertiary. With increased neutral stabilization, the fault current in the neutral on single-phase short circuit is increased, and this may be needed for improved relay protection of the system.
Third-harmonic components of exciting current find a relatively low impedance path in a delta tertiary on a Y-connected transformer, and less of the third-harmonic exciting current appears in the connected transmission lines, where it might cause interference with communication circuits. Failure to provide a path for third-harmonic current in Y-connected 3-phase shell-type transformers or banks of single-phase transformers will result in excessive third-harmonic voltage from line to neutral.
The bank of a 3-phase, three-legged core-type Y-connected transformer acts as a delta winding with high impedance to the other windings. As a consequence, there is very little third-harmonic line-to-neutral voltage and a separate delta tertiary is not needed to reduce it. An external load can be supplied from a delta tertiary. This may include synchronous or static capacitors to improve system operating conditions.
DELTA – DELTA (ΔΔ) CLOSED / NEUTRAL = PRIM NO-SEC YES TRANSFORMER CONNECTION TUTORIALS AND BASIC INFORMATION
WHERE USED
For supplying three-phase, 240-volt
loads with small amounts of 120/240-volt, single-phase load. No
problem from third harmonic overvoltage or telephone interference.
With a disabled unit, bank can be reconnected in open-delta for
emergency service.
DELTA-DELTA FOR LIGHTING AND POWER
This connection is often used to supply
a small single-phase lighting load and three-phase power load
simultaneously. As shown is diagram, the mid-tap of the secondary of
one transformer is grounded.
Thus, the small lighting load is
connected across the transformer with the mid-tap and the ground wire
common to both 120 volt circuits. The single-phase lighting load
reduces the available three-phase capacity. This connection requires
special watt-hour metering and is not available from all utilities.
DIAGRAM
BANK RATING
The transformer with the mid-tap
carries 2/3 of the 120/240-volt, single-phase load and 1/3 of the
240-volt, three-phase load. The other two units each carry 1/3 of
both the 120/240- and 240-volt loads.
CAUTION
High circulating currents will result
unless all units are connected on same regulating taps and have same
voltage ratios. Bank rating is reduced unless matching impedance
transformers are used. The secondary neutral bushing can be grounded
on only one of the three transformers.
IMPEDANCE
When three transformers are operated in
a closed-delta bank, care should be taken to make certain the
impedances of the three units are practically the same. Transformers
having more than 10% difference in impedance rating should not be
operated together in a closed-delta bank unless a reactor is used to
increase the impedance of the unit having the lower impedance rating
to a value equal to the other units.
If the voltage ratio of all three of
the transformers is not the same, there will be a voltage tending to
circulate current inside the delta. The current will be limited by
the impedance of the three transformers considered as a series
circuit.
It is a good practice, before applying
voltage to three transformers in closed delta, to insert a fuse wire
between the leads coming from the high-voltage bushings of two
transformers closing the delta bank. The fuse wire should be of
sufficient size to carry the exciting current of the transformers.
The use of this fuse wire offers a very
simple means of making certain the transformers have the proper
polarity.
This connection should not be used with
CSP transformers if used to supply a combined three-phase and
three-wire single-phase load due to unequal voltage division of
single-phase load when the tapped transformer breaker is opened.
HIGH-LEG MARKING
NEC 2002: 110.15 High-Leg Marking.
On a 4-wire, delta-connected system
where the midpoint of one phase winding is grounded to supply
lighting and similar loads, the conductor or busbar having the higher
phase voltage to ground shall be durably and permanently marked by an
outer finish that is orange in color or by other effective means.
Such identification shall be placed at each point on the system where
a connection is made if the grounded conductor is also present.
NEC 2002 Handbook:
Added for the 2002 Code, this section
now contains a requirement that appeared in 384-3(e) of the 1999 NEC.
This requirement was moved to Article 110, where the application
becomes a more general requirement.
The high leg is common on a
240/120-volt 3-phase, 4-wire delta system. It is typically designated
as “B phase.” The high-leg marking is required to be the color
orange or other similar effective means and is intended to prevent
problems due to the lack of complete standardization where metered
and non-metered equipment are installed in the same installation.
Electricians should always test each phase relative to ground with
suitable equipment to determine exactly where the high leg is located
in the system.
ARRANGEMENT OF BUSBARS AND
CONDUCTORS
NEC 2002: 408.3 / Support and
Arrangement of Busbars and Conductors / (E) Phase Arrangement
The phase arrangement on 3-phase buses
shall be A, B, C from front to back, top to bottom, or left to right,
as viewed from the front of the switchboard or panelboard.
The B phase shall be that phase having
the higher voltage to ground on 3-phase, 4-wire, delta-connected
systems. Other busbar arrangements shall be permitted for additions
to existing installations and shall be marked.
Exception: Equipment within the same
single section or multisection switchboard or panelboard as the meter
on 3-phase, 4-wire, delta-connected systems shall be permitted to
have the same phase configuration as the metering equipment.
FPN: See 110.15 for requirements on
marking the busbar or phase conductor having the higher voltage to
ground where supplied from a 4-wire, delta-connected system.
NEC 2002 Handbook:
The high leg is common on a
240/120-volt, 3-phase, 4-wire delta system. It is typically
designated as “B phase.” Section 110.15 requires the high-leg
marking to be the color orange or other similar effective means of
identification. Electricians should always test each phase to ground
with suitable equipment in order to know exactly where this high leg
is located in the system.
The exception to 408.3(E) permits the
phase leg having the higher voltage to ground to be located at the
right-hand position (C phase), making it unnecessary to transpose the
panelboard or switchboard busbar arrangement ahead of and beyond a
metering compartment. The exception recognizes the fact that metering
compartments have been standardized with the high leg at the right
position (C phase) rather than in the center on B phase.
See also 110.15, 215.8, and 230.56 for
further information on identifying conductors with the higher voltage
to ground. Other busbar arrangements for making additions to existing
installations are permitted by 408.3(E).
POWER TRANSFORMER WINDING CONNECTION DIAGRAM
The actual winding connections are
shown in a diagram with each winding and its taps labeled. A set of
tables then specifies the voltage ratings, ampere ratings, and the
connections for all the available taps. For transformers with load
tap changing equipment, the connection diagrams and the accompanying
tables are quite extensive.
The connection diagram usually also
gives the general physical layout of the transformer, showing the
placement of the bushings and the locations of current transformers
(CTs) and a schematic representation of the load tap changing
equipment, including the preventative autotransformer, moving
contacts, arcing contacts, transfer switch, and reversing switch.
A portion of an actual nameplate that
shows the winding connection diagram is illustrated in Figure 7.2.
The nameplate depicted is rather interesting. The transformer has a
load tap changer.
From the connection diagram we see that
the buried tertiary is also a tapped winding that supplies a
buck/boost voltage to the secondary windings through auxiliary
transformers connected between the tertiary and the secondary.
Therefore, the tertiary simultaneously
provides four important functions:
1. It provides a path for third
harmonic currents.
2. It helps stabilize voltages in the
Y-Y primary-secondary connection.
3. It provides a grounding bank action
by providing a path for zero sequence currents.
4. It provides the necessary voltage
taps for regulating the low-side voltage.
The only function that the buried
tertiary cannot perform is to supply an external load. The voltage
rating of the buried tertiary is not given because it cannot be
connected to a system voltage, but one corner of the Δ connection is
grounded internally.
This grounding is done so the winding
potential voltage does not ‘‘float’’ because of capacitive
coupling to the other windings. Without this ground connection,
capacitively induced voltages are indeterminate and could be large
enough to cause insulation damage.
The voltage taps for the primary and
secondary are shown on the connection diagram and on the winding
rating tables in Figure 7.2. These also specify which terminal
numbers and letters are connected for each tap.
This transformer has a total of 14
current transformers that are used for metering, protective relaying,
and other purposes. Note the CTs marked ‘‘LDC’’ and ‘‘WDG.
TEMP.’’ The term LDC stands for line drop compensation. The LDC
CT supplies metered line current to a compensating device in the
voltage regulator controls.
The compensating device effectively
moves the voltage control point into the system connected to the
secondary winding. The CT labeled WDG.TEMP supplies current to the
winding temperature gauges.
These gauges use a heating element
surrounding a temperature probe mounted in the top oil in order to
mimic the winding temperature. The ratios of these CTs would be shown
on an actual nameplate, but this information is not shown in Figure
7.2.
Just below the connection diagram is a
layout sketch showing the physical locations of the bushings, the
load tap changing compartment and the operating handle for the tap
changer at deenergized conditions. The load tap changer is
represented schematically in the connection diagram.
Note the terminals labeled P1, P2, and
P3. These terminals correspond to the connections to the preventative
autotransformer. The two series arcing contacts per phase that are in
series with the movable contacts are shown as well.
FIGURE 7.2 Part of a transformer’s
nameplate showing the voltage ratings, MVA ratings, percent
impedances, connection diagram, physical layout, vector diagram, tap
connections, CT connections, and BIL ratings.
OPEN DELTA CONNECTION FOR LIGHT AND POWER BASIC AND TUTORIALS
Standard Connection
When the secondary circuits are to supply both light and power, the open-delta bank takes this form. In addition to the applications listed above for the open-delta bank for power, this type of bank is used where there is a large single-phase load and only a small three-phase load.
In this case, the two transformers would be of of different kva sizes, the one across which the lighting load is connected being the larger. This is also the connection that should be used when protected transformers are employed in a three-phase bank supplying both light and power.
Simplified Connection
This is similar to the connection above but gives a nonstandard 180° angular displacement. Otherwise the information given above is applicable to this connection.
EQUIVALENT CIRCUIT OF A THREEWINDING TRANSFORMER BASICS AND TUTORIALS
EQUIVALENT CIRCUIT OF A THREE WINDING TRANSFORMER BASIC INFORMATION
What Is The Equivalent Circuit Of A Three Winding Transformer?
Various forms of a three-winding transformer equivalent circuit have been proposed, but the simplest and most useful is the so-called T equivalent circuit, shown in Figure 4.9.
The magnetizing branch is omitted in the T equivalent since the magnetizing impedance is normally much greater than the series impedances. If voltages and impedances are expressed in per unit values, then the ideal transformers can sometimes be omitted also; however, in some cases 1:1 ideal transformers are retained so that the connections to the primary, secondary and tertiary circuits can be properly represented by the equivalent circuit.
In a three-winding transformer, eddy-current losses occur in each winding from stray flux produced by the other two windings, even if the third winding is not carrying any load. Therefore, each series resistance element in the T equivalent circuit of a three-winding transformer represent eddy-current losses produced by currents in other windings.
Hence, a series resistance does not belong to any particular winding but is distributed among all three widings. To derive the series impedance values in the T equivalent circuit, impedance measurements are made of each pair of windings taken two at a time.
One winding is short-circuited with voltage applied to the other winding while the third winding is open-circuited. The current is measured through the winding with the applied voltage. The impedance is equal to the applied voltage divided by that current.
The test setup to measure the impedance between the H and X windings of a single-phase three-winding transformer is shown in Figure 4.10.
What Is The Equivalent Circuit Of A Three Winding Transformer?
Various forms of a three-winding transformer equivalent circuit have been proposed, but the simplest and most useful is the so-called T equivalent circuit, shown in Figure 4.9.
The magnetizing branch is omitted in the T equivalent since the magnetizing impedance is normally much greater than the series impedances. If voltages and impedances are expressed in per unit values, then the ideal transformers can sometimes be omitted also; however, in some cases 1:1 ideal transformers are retained so that the connections to the primary, secondary and tertiary circuits can be properly represented by the equivalent circuit.
In a three-winding transformer, eddy-current losses occur in each winding from stray flux produced by the other two windings, even if the third winding is not carrying any load. Therefore, each series resistance element in the T equivalent circuit of a three-winding transformer represent eddy-current losses produced by currents in other windings.
Hence, a series resistance does not belong to any particular winding but is distributed among all three widings. To derive the series impedance values in the T equivalent circuit, impedance measurements are made of each pair of windings taken two at a time.
One winding is short-circuited with voltage applied to the other winding while the third winding is open-circuited. The current is measured through the winding with the applied voltage. The impedance is equal to the applied voltage divided by that current.
The test setup to measure the impedance between the H and X windings of a single-phase three-winding transformer is shown in Figure 4.10.
The test for a three-phase, three-winding transformer is similar except that three-phase voltages are used. There are three sets of measurements taken.
The first set of measurements applies a three-phase voltage to the H1, H2, and H3 terminals with the X1, X2, and X3 terminals shorted together and the Y1, Y2, and Y3 terminals open.
The second set of measurements applies a three-phase voltage to the H1, H2, and H3 terminals with the Y1, Y2, and Y3 terminals shorted together and the X1, X2, and X3 terminals open.
Finally, a three-phase voltage is applied to the X1, X2 and X3 terminals with the Y1, Y2, and Y3 terminals shorted together with the H1, H2, and H3 terminals open. The ZHX, ZHY, and ZXY impedance values are determined by dividing the voltages by the currents in each test.
THREE WINDING TRANSFORMER BASIC INFORMATION
What Is Three Winding Transformer?
The three-winding transformer is a subset of multiwinding transformers. In addition to the usual primary and secondary windings, a third tertiary winding is added to each phase. Having three winding can serve several purposes:
• Three windings allow connecting three systems together where each system has a different operating voltage.
• Three windings provide electrical isolation between dual input circuits or dual output circuits having the same operating voltage.
• If the third winding is Δ-connected, this can stabilize voltages, supply third harmonic currents to magnetize the transformer core, filter third harmonics from the system, and provide grounding bank action when the primary and secondary windings are both Y-connected.
Sometimes a tertiary winding may serve more than one function at the same time. For example, a 13.8 kV Δ-connected tertiary winding on a 230 kV– 69 kV Grd.Y-Grd.Y transformer helps to stabilize the primary and secondary voltages, provides grounding bank action to partially shield the primary circuit from secondary ground currents, and provides 13.8 kV supply voltage to a station-service auxiliary transformer.
(Note: When a group of windings are connected in parallel to increase the current capability of a secondary winding, the parallel group is considered one winding and not several separate windings. Using multiple sets of low-voltage windings in parallel is common in large generator step-up transformers; however, these are still considered two winding transformers.)
Sometimes a tertiary winding is intended only to magnetically interact with the primary and secondary windings so it may not have any external terminal connections. In these cases, the tertiary winding is said to be an imbedded tertiary.
Imbedded tertiary windings are found only in three-phase transformers and are always Δ-connected. One corner of the Δ-connected imbedded tertiary winding is sometimes grounded internally to limit capacitively coupled voltages.
For single-phase transformers, the standard labels for the tertiary bushings are Y1 and Y2. For three-phase transformers, the standard labels for the tertiary bushings are (Y0), Y1, Y2, Y3.
What Is Three Winding Transformer?
The three-winding transformer is a subset of multiwinding transformers. In addition to the usual primary and secondary windings, a third tertiary winding is added to each phase. Having three winding can serve several purposes:
• Three windings allow connecting three systems together where each system has a different operating voltage.
• Three windings provide electrical isolation between dual input circuits or dual output circuits having the same operating voltage.
• If the third winding is Δ-connected, this can stabilize voltages, supply third harmonic currents to magnetize the transformer core, filter third harmonics from the system, and provide grounding bank action when the primary and secondary windings are both Y-connected.
Sometimes a tertiary winding may serve more than one function at the same time. For example, a 13.8 kV Δ-connected tertiary winding on a 230 kV– 69 kV Grd.Y-Grd.Y transformer helps to stabilize the primary and secondary voltages, provides grounding bank action to partially shield the primary circuit from secondary ground currents, and provides 13.8 kV supply voltage to a station-service auxiliary transformer.
(Note: When a group of windings are connected in parallel to increase the current capability of a secondary winding, the parallel group is considered one winding and not several separate windings. Using multiple sets of low-voltage windings in parallel is common in large generator step-up transformers; however, these are still considered two winding transformers.)
Sometimes a tertiary winding is intended only to magnetically interact with the primary and secondary windings so it may not have any external terminal connections. In these cases, the tertiary winding is said to be an imbedded tertiary.
Imbedded tertiary windings are found only in three-phase transformers and are always Δ-connected. One corner of the Δ-connected imbedded tertiary winding is sometimes grounded internally to limit capacitively coupled voltages.
For single-phase transformers, the standard labels for the tertiary bushings are Y1 and Y2. For three-phase transformers, the standard labels for the tertiary bushings are (Y0), Y1, Y2, Y3.
ADVANTAGES AND DISADVANTAGES OF THE AUTOTRANSFORMER CONNECTION
AUTOTRANSFORMERS CONNECTION ADVANTAGES AND DISADVANTAGES
What Are The Advantages And Disadvantages Of Autotransformer Connection?
Summarizing the advantages of the autotransformer connection:
• There are considerable savings in size and weight.
• There are decreased losses for a given KVA capacity.
• Using an autotransformer connection provides an opportunity for achieving lower series impedances and better regulation.
Summarizing the disadvantages of the autotransformer connection:
• The autotransformer connection is not available with certain threephase connections.
• Higher (and possibly more damaging) short-circuit currents can result from a lower series impedance.
• Short circuits can impress voltages significantly higher than operating voltages across the windings of an autotransformer.
• For the same voltage surge at the line terminals, the impressed and induced voltages are greater for an autotransformer than for a two winding transformer.
In many instances, the advantages of the autotransformer connection outweigh its disadvantages.
For example, when very large MVA capability is required and where a Grd.Y-Grd.Y connection is suitable, an autotransformer is usually the design of choice.
Because an autotransformer cannot provide a Δ-Y connection, autotransformers are not suitable for use as generator step-up transformers.
What Are The Advantages And Disadvantages Of Autotransformer Connection?
Summarizing the advantages of the autotransformer connection:
• There are considerable savings in size and weight.
• There are decreased losses for a given KVA capacity.
• Using an autotransformer connection provides an opportunity for achieving lower series impedances and better regulation.
Summarizing the disadvantages of the autotransformer connection:
• The autotransformer connection is not available with certain threephase connections.
• Higher (and possibly more damaging) short-circuit currents can result from a lower series impedance.
• Short circuits can impress voltages significantly higher than operating voltages across the windings of an autotransformer.
• For the same voltage surge at the line terminals, the impressed and induced voltages are greater for an autotransformer than for a two winding transformer.
In many instances, the advantages of the autotransformer connection outweigh its disadvantages.
For example, when very large MVA capability is required and where a Grd.Y-Grd.Y connection is suitable, an autotransformer is usually the design of choice.
Because an autotransformer cannot provide a Δ-Y connection, autotransformers are not suitable for use as generator step-up transformers.
ZIGZAG CONNECTION OF TRANSFORMER BASICS AND TUTORIALS
ZIGZAG TRANSFORMER CONNECTION BASIC INFORMATION
What Is Zigzag Transformer? What Is Zigzag Connection Of Transformers?
The zigzag connection is also called the interconnected star connection. This connection has some of the features of the Y and the Δ connections, combining the advantages of both. The zigzag connection is a three-phase connection and is constructed as shown in Figure 2.14.
There are three pairs of windings, each having a 1:1 turns ratio. The left-hand set of windings shown in the
figure is a conventional Y connection, a′-b′-c′, with the neutral N brought out.
The open ends of the Y are electrically connected to the right-hand set of windings as follows: a′ connects to the right-hand winding paired with to the b′-N winding, b′ connects to the right-hand winding paired to c′-N winding, and c′ connects to the right-hand winding paired to the a′-N winding.
The opposite ends of the right-hand windings are brought out as the phase terminals a, b, and c. The vector diagram shown on the right of Figure 2.14 makes it is obvious why this is called a zigzag connection. It operates on the following principle:
If three currents, equal in magnitude and phase, are applied to the three terminals, the ampere-turns of the a′-N winding cancel the ampere-turns of the c′- c winding, the ampere-turns of the b′-N winding cancel the ampere turns of the a′-a winding, and the ampere-turns of the c′-N winding cancel the ampere turns of the b′-b winding. Therefore, the transformer allows the three in-phase currents to easily flow to neutral.
If three currents, equal in magnitude but 120° out of phase with each other, are applied to the three terminals, the ampere-turns in the windings cannot cancel and the transformer restricts the current flow to the negligible level of magnetizing current.
Therefore, the zigzag winding provides an easy path for in-phase currents but does not allow the flow of currents that are 120° out of phase with each other.
The ability to provide a path for in-phase currents enables us to use the zigzag connection as a grounding bank, which is one of the main applications for this connection. If a zigzag winding is used as a secondary winding with a Δ winding used as a primary winding, the Δ-zigzag connection is created, as show nin Figure 2.15.
AΔ-zigzag transformer is technically not a two-winding transformer but rather a three-winding transformer because three separate windings are wound around each core leg. Since two of the sets of windings are interconnected, we treat the Δ-zigzag as if it were a two-winding transformer.
As usual, the sets of windings that are magnetically linked on common core legs are drawn in parallel to each other, as shown in Figure 2.15.
The Δ-zigzag connection provides the same advantages as the Δ-Y connection, like third harmonic suppression and ground current isolation. One added advantage is that there is no phase angle displacement between the primary and the secondary circuits with this connection; therefore, the Δ-zigzag connection can be used in the same manner as Y-Y and Δ-Δ transformers without introducing any phase shifts in the circuits.
What Is Zigzag Transformer? What Is Zigzag Connection Of Transformers?
The zigzag connection is also called the interconnected star connection. This connection has some of the features of the Y and the Δ connections, combining the advantages of both. The zigzag connection is a three-phase connection and is constructed as shown in Figure 2.14.
There are three pairs of windings, each having a 1:1 turns ratio. The left-hand set of windings shown in the
figure is a conventional Y connection, a′-b′-c′, with the neutral N brought out.
The open ends of the Y are electrically connected to the right-hand set of windings as follows: a′ connects to the right-hand winding paired with to the b′-N winding, b′ connects to the right-hand winding paired to c′-N winding, and c′ connects to the right-hand winding paired to the a′-N winding.
The opposite ends of the right-hand windings are brought out as the phase terminals a, b, and c. The vector diagram shown on the right of Figure 2.14 makes it is obvious why this is called a zigzag connection. It operates on the following principle:
If three currents, equal in magnitude and phase, are applied to the three terminals, the ampere-turns of the a′-N winding cancel the ampere-turns of the c′- c winding, the ampere-turns of the b′-N winding cancel the ampere turns of the a′-a winding, and the ampere-turns of the c′-N winding cancel the ampere turns of the b′-b winding. Therefore, the transformer allows the three in-phase currents to easily flow to neutral.
If three currents, equal in magnitude but 120° out of phase with each other, are applied to the three terminals, the ampere-turns in the windings cannot cancel and the transformer restricts the current flow to the negligible level of magnetizing current.
Therefore, the zigzag winding provides an easy path for in-phase currents but does not allow the flow of currents that are 120° out of phase with each other.
The ability to provide a path for in-phase currents enables us to use the zigzag connection as a grounding bank, which is one of the main applications for this connection. If a zigzag winding is used as a secondary winding with a Δ winding used as a primary winding, the Δ-zigzag connection is created, as show nin Figure 2.15.
AΔ-zigzag transformer is technically not a two-winding transformer but rather a three-winding transformer because three separate windings are wound around each core leg. Since two of the sets of windings are interconnected, we treat the Δ-zigzag as if it were a two-winding transformer.
As usual, the sets of windings that are magnetically linked on common core legs are drawn in parallel to each other, as shown in Figure 2.15.
The Δ-zigzag connection provides the same advantages as the Δ-Y connection, like third harmonic suppression and ground current isolation. One added advantage is that there is no phase angle displacement between the primary and the secondary circuits with this connection; therefore, the Δ-zigzag connection can be used in the same manner as Y-Y and Δ-Δ transformers without introducing any phase shifts in the circuits.
Subscribe to:
Comments (Atom)
Previous Articles
-
▼
2025
(123)
-
▼
October
(123)
- Understanding Tensile and Compressive Forces in Wi...
- Understanding Axial Forces in Power Transformer De...
- Understanding the Dynamics of Winding Forces in El...
- Understanding Short-Circuit Forces in Power Transf...
- Understanding the Forces on Conductors in Power Tr...
- Ensuring Transformer Efficiency: Cooling Technique...
- Understanding Oil Flow and Temperature Distributio...
- Understanding Eddy Current Loss and Cooling in Pow...
- Understanding Winding Hot Spot Rise in Transformers
- Understanding Temperature Dynamics in Power Transf...
- Understanding Transformer Cooling: The Role of Dir...
- Understanding Radiator Placement and Cooling Metho...
- Understanding Transformer Cooling: The Role of Oil...
- Understanding Transformer Winding Hot Spot Factors...
- Enhancing Transformer Longevity with Natural Ester...
- Understanding Inrush Current in Transformer Operation
- Understanding Transformer Core Characteristics and...
- Understanding the Impact of Third Harmonic Voltage...
- Understanding No-Load Losses in Cold-Rolled Lamina...
- Understanding No-Load Loss in Transformer Core Design
- Understanding Transformer Design: Key Factors in E...
- Exploring the Dynamics of Steel in Transformer Cores
- Understanding Power Transformer Design: Key Concep...
- Understanding Transformer Design: Balancing Effici...
- Understanding Transformer Connections: A Primer on...
- Understanding the Winding Space Factor in Transfor...
- Understanding Load Loss and Transformer Design: A ...
- Understanding Tap Changers: Enhancing Transformer ...
- Understanding Transformer Efficiency and Voltage R...
- Understanding Transformer Impedance: Key Concepts ...
- Understanding Transformer Losses: No-Load and Load...
- Understanding Power Transformers: Insights into Th...
- Understanding Power Transformers: The Backbone of ...
- Understanding Load Losses and Impedance in Power T...
- Exploring the Intricacies of Magnetism and Sound i...
- Understanding Oil Thermal Behavior and Short-Circu...
- Understanding Insulation and Impedance in Electric...
- Understanding Transformer Insulation: Key Concepts...
- Understanding Transformer Winding Connections and ...
- Understanding Power Transformer Design Practices: ...
- Understanding the Load Loss Test in Power Transfor...
- Understanding Eddy Current Losses in Metals: A Com...
- Understanding Power Loss in Structural Components:...
- Understanding Eddy Loss in Structural Plates: A De...
- Understanding Eddy Currents and Stray Losses in Ma...
- Understanding Stray Losses in Transformers: The Ro...
- Understanding Stray Losses in Transformer Design
- Understanding Eddy Currents and Stray Losses in Po...
- Understanding Flux Density and Over-Excitation in ...
- Understanding Transformer Excitation and Losses: A...
- Understanding Core Loss in Transformers: The Role ...
- Understanding Core Losses in Magnetic Circuits: Hy...
- Understanding Core Losses in Electrical Transformers
- Understanding Zero-Sequence Impedance and Core Con...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Core Designs: A Deep Div...
- Understanding Transformer Vector Groups: A Key to ...
- Understanding Parallel Operation of Transformers: ...
- Understanding Transformer Ratings: Why Volt-Ampere...
- Understanding Transformer Circuit Parameters and E...
- Understanding Transformer Efficiency and Regulation
- Understanding Transformer Short-Circuit Testing an...
- Understanding Transformer Parameters: The Per-Unit...
- Understanding Transformer Representation in Power ...
- Understanding Core Magnetization and Losses in Tra...
- Understanding Practical Transformers: The Mechanic...
- Understanding Ideal Transformer Behavior: A Deep D...
- Understanding Transformers: The Key to Electromagn...
- Understanding Transformers and Reactors: The Backb...
- Understanding Distribution Transformers: Types and...
- Understanding Transformer Fundamentals: Types and ...
- Understanding Transformer Technology: Insights and...
- Understanding SF6 Transformers: Benefits and Chall...
- Understanding Transformer Technology: Materials, D...
- Exploring Specialized Transformers: Beyond the Basics
- Understanding Transformer Design: Key Concepts and...
- Unlocking the Secrets of Transformer Engineering
- Unraveling Transformer Technology: A New Era of In...
- Unlocking Transformer Engineering: Insights from K...
- Exploring the Latest Advancements in Transformer T...
- Unraveling Transformer Engineering: Insights from ...
- Understanding Transformer Engineering: Key Insight...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Pad-Mounted Distribution Transformer...
- Understanding Submersible Transformers: Key Featur...
- Understanding Submersible Transformers: Types and ...
- Understanding Transformers: The Backbone of Electr...
- Understanding Vault Installations: The Backbone of...
- Understanding Underground Transformers: A Key Comp...
- Understanding Transformer Polarity and Standards: ...
- Understanding Operational Concerns in Transformer ...
- Understanding Transformer Connections: A Guide to ...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Configurations: A Guide ...
- Advancements in Transformer Design: From Adhesives...
- Understanding Transformer Coolants and Materials: ...
- Understanding the Evolution of Distribution Transf...
- The Evolution of Transformer Core Technology: A Lo...
- The Evolution of Distribution Transformers: From I...
- Innovations in Transformer Design: Paving the Way ...
-
▼
October
(123)









