The following technical terms apply to transformers.
BIL: An abbreviation for basic impulse level, a dielectric strength test. Transformer BIL is determined by applying a high-frequency square-wave voltage with a steep leading edge between the windings and between the windings and ground.
The BIL rating provides the maximum input kV rating that a transformer can withstand without causing insulation breakdown. The transformer must also be protected against natural or man-made electrical surges. The NEMA standard BIL rating is 10 kV.
Exciting current: In transformers, the current in amperes required for excitation. This current consists of two components: (1) real in the form of losses (no load watts) and (2) reactive power in kvar. Exciting current varies inversely with kVA rating from approximately 10 percent at 1 kVA to as low as 0.5 percent at 750 kVA.
Eddy-current losses: Contiguous energy losses caused when a varying magnetic flux sets up undesired eddy currents circulating in a ferromagnetic transformer core.
Hysteresis losses: Continuous energy losses in a ferromagnetic transformer core when it is taken through the complete magnetization cycle at the input frequency.
Insulating transformer: A term synonymous with isolating transformer, to describe the insulation or isolation between the primary and secondary windings. The only transformers that are not insulating or isolating are autotransformers. Insulation system temperature: The maximum temperature in degrees Celsius at the hottest point in the winding.
Isolating transformer: See insulating transformer. Shielded-winding transformer: A transformer with a conductive metal shield between the primary and secondary windings to attenuate transient noise.
Taps: Connections made to transformer windings other than at its terminals. They are provided on the input side of some high-voltage transformers to correct for high or low voltages so that the secondary terminals can deliver their full rated output voltages.
Temperature rise: The incremental temperature rise of the windings and insulation above the ambient temperature.
Transformer impedance: The current-limiting characteristic of a transformer expressed as a percentage. It is used in determining the interrupting capacity of a circuit breaker or fuse that will protect the transformer primary.
Transformer voltage regulation: The difference between the no-load and full-load voltages expressed as a percentage. A transformer that delivers 200 V at no load and 190 V at full load has a regulation of 5 percent.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Showing posts with label Transformer Studies. Show all posts
Showing posts with label Transformer Studies. Show all posts
POWER TRANSFORMER DIELECTRIC TESTS TYPES BASIC INFORMATION
Low-Frequency Tests
There are two low-frequency tests:
1. Low-frequency wet-withstand voltage
test
2. Low-frequency dry-withstand voltage
test
Low-Frequency Wet-Withstand Voltage
Test — The low-frequency wet-withstand voltage test is applied
on bushings rated 242 kV and below while a waterfall at a particular
precipitation rate and conductivity is applied. The values of
precipitation rate, water resistivity, and the time of application
vary in different countries.
American standard practice is a
precipitation rate of 5 mm/min, a resistivity of 178 ohm-m, and a
test duration of 10 sec, whereas European practice is 3 mm/min, 100
ohm��m, and 60 sec, respectively.
If the bushing flashes over externally
during the test, it is allowed that the test be applied one
additional time. If this attempt also flashes over, then the test
fails and something must be done to modify the bushing design or test
setup so that the capability can be established.
Low-Frequency Dry-Withstand Voltage
Test — The low-frequency dry-withstand test was, until
recently, made for a 1-min duration without the aid of
partial-discharge measurements to detect incipient failures, but
standards currently specify a one-hour duration for the design test,
in addition to partial-discharge measurements.
The present test procedure is:
Partial discharge (either
radio-influence voltage or apparent charge) shall be measured at 1.5
times the maximum line-ground voltage. Maximum limits for partial
discharge vary for different bushing constructions and range from 10
to 100 ��V or pC.
A 1-min test at the dry-withstand
level, approximately 1.7 times the maximum line-ground voltage, is
applied. If an external flashover occurs, it is allowed to make
another attempt, but if this one also fails, the bushing fails the
test. No partial-discharge tests are required for this test.
Partial-discharge measurements are
repeated every 5 min during the one-hour test duration at 1.5 times
maximum line-ground voltage required for the design test. Routine
tests specify only a measurement of partial discharge at 1.5 times
maximum line-ground voltage, after which the test is considered
complete.
Bushing standards were changed in the
early 1990s to align with the transformer practice, which started to
use the one-hour test with partial-discharge measurements in the late
1970s. Experience with this new approach has been good in that
incipient failures were uncovered in the factory test laboratory,
rather than in service, and it was decided to add this procedure to
the bushing test procedure.
Also from a more practical standpoint,
bushings are applied to every transformer, and transformer
manufacturers require that these tests be applied to the bushings
prior to application so as to reduce the number of bushing failures
during the transformer tests.
TRANSFORMER INRUSH EFFECTS STUDIES DOWNLOAD LINK
DOWNLOAD LINK OF STUDIES ON TRANSFORMER INRUSH EFFECTS
Transformer Inrush Studies Link
Introduction
In a typical UK wind farm a series of radial 33kV collector circuits run from the main switchboard and link together individual wind turbine generator (WTG) transformers. At the design stage it is necessary to determine the maximum number of WTG transformers that can be energised simultaneously from the 33kV system.
One of the factors to be considered is the voltage dip experienced at the point of common coupling (PCC) or interface between the electrical system of the wind farm and the utility company. The UK standard applied is the Electricity Council’s Engineering Recommendation P28, which allows a 3% voltage dip. This article describes wind farm transformer inrush analysis studies the Glasgow based power systems consultants Mott MacDonald have undertaken using PSCAD to demonstrate compliance with P28.
Transformer inrush
When a transformer is energised, it may draw a high magnitude transient current from the supply causing a temporary voltage dip. This current, characterised as being almost entirely unidirectional, rises abruptly to its maximum value in the first half-cycle and then decays until the normal steady-state magnetizing conditions are reached. The magnitude and duration of the inrush current depends upon the following all of which can be represented using a PSCAD model:
the point on the voltage wave at the instant the transformer is energised (i.e. switching angle);
the impedance of the supply circuit;
the value and sign of the residual flux linkage in the core;
the non-linear magnetic saturation characteristic of the core.
VIEW THE ENTIRE DOCUMENT HERE!!!
Transformer Inrush Studies Link
Introduction
In a typical UK wind farm a series of radial 33kV collector circuits run from the main switchboard and link together individual wind turbine generator (WTG) transformers. At the design stage it is necessary to determine the maximum number of WTG transformers that can be energised simultaneously from the 33kV system.
One of the factors to be considered is the voltage dip experienced at the point of common coupling (PCC) or interface between the electrical system of the wind farm and the utility company. The UK standard applied is the Electricity Council’s Engineering Recommendation P28, which allows a 3% voltage dip. This article describes wind farm transformer inrush analysis studies the Glasgow based power systems consultants Mott MacDonald have undertaken using PSCAD to demonstrate compliance with P28.
Transformer inrush
When a transformer is energised, it may draw a high magnitude transient current from the supply causing a temporary voltage dip. This current, characterised as being almost entirely unidirectional, rises abruptly to its maximum value in the first half-cycle and then decays until the normal steady-state magnetizing conditions are reached. The magnitude and duration of the inrush current depends upon the following all of which can be represented using a PSCAD model:
the point on the voltage wave at the instant the transformer is energised (i.e. switching angle);
the impedance of the supply circuit;
the value and sign of the residual flux linkage in the core;
the non-linear magnetic saturation characteristic of the core.
VIEW THE ENTIRE DOCUMENT HERE!!!
Subscribe to:
Comments (Atom)
Previous Articles
-
▼
2025
(123)
-
▼
October
(123)
- Understanding Tensile and Compressive Forces in Wi...
- Understanding Axial Forces in Power Transformer De...
- Understanding the Dynamics of Winding Forces in El...
- Understanding Short-Circuit Forces in Power Transf...
- Understanding the Forces on Conductors in Power Tr...
- Ensuring Transformer Efficiency: Cooling Technique...
- Understanding Oil Flow and Temperature Distributio...
- Understanding Eddy Current Loss and Cooling in Pow...
- Understanding Winding Hot Spot Rise in Transformers
- Understanding Temperature Dynamics in Power Transf...
- Understanding Transformer Cooling: The Role of Dir...
- Understanding Radiator Placement and Cooling Metho...
- Understanding Transformer Cooling: The Role of Oil...
- Understanding Transformer Winding Hot Spot Factors...
- Enhancing Transformer Longevity with Natural Ester...
- Understanding Inrush Current in Transformer Operation
- Understanding Transformer Core Characteristics and...
- Understanding the Impact of Third Harmonic Voltage...
- Understanding No-Load Losses in Cold-Rolled Lamina...
- Understanding No-Load Loss in Transformer Core Design
- Understanding Transformer Design: Key Factors in E...
- Exploring the Dynamics of Steel in Transformer Cores
- Understanding Power Transformer Design: Key Concep...
- Understanding Transformer Design: Balancing Effici...
- Understanding Transformer Connections: A Primer on...
- Understanding the Winding Space Factor in Transfor...
- Understanding Load Loss and Transformer Design: A ...
- Understanding Tap Changers: Enhancing Transformer ...
- Understanding Transformer Efficiency and Voltage R...
- Understanding Transformer Impedance: Key Concepts ...
- Understanding Transformer Losses: No-Load and Load...
- Understanding Power Transformers: Insights into Th...
- Understanding Power Transformers: The Backbone of ...
- Understanding Load Losses and Impedance in Power T...
- Exploring the Intricacies of Magnetism and Sound i...
- Understanding Oil Thermal Behavior and Short-Circu...
- Understanding Insulation and Impedance in Electric...
- Understanding Transformer Insulation: Key Concepts...
- Understanding Transformer Winding Connections and ...
- Understanding Power Transformer Design Practices: ...
- Understanding the Load Loss Test in Power Transfor...
- Understanding Eddy Current Losses in Metals: A Com...
- Understanding Power Loss in Structural Components:...
- Understanding Eddy Loss in Structural Plates: A De...
- Understanding Eddy Currents and Stray Losses in Ma...
- Understanding Stray Losses in Transformers: The Ro...
- Understanding Stray Losses in Transformer Design
- Understanding Eddy Currents and Stray Losses in Po...
- Understanding Flux Density and Over-Excitation in ...
- Understanding Transformer Excitation and Losses: A...
- Understanding Core Loss in Transformers: The Role ...
- Understanding Core Losses in Magnetic Circuits: Hy...
- Understanding Core Losses in Electrical Transformers
- Understanding Zero-Sequence Impedance and Core Con...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Core Designs: A Deep Div...
- Understanding Transformer Vector Groups: A Key to ...
- Understanding Parallel Operation of Transformers: ...
- Understanding Transformer Ratings: Why Volt-Ampere...
- Understanding Transformer Circuit Parameters and E...
- Understanding Transformer Efficiency and Regulation
- Understanding Transformer Short-Circuit Testing an...
- Understanding Transformer Parameters: The Per-Unit...
- Understanding Transformer Representation in Power ...
- Understanding Core Magnetization and Losses in Tra...
- Understanding Practical Transformers: The Mechanic...
- Understanding Ideal Transformer Behavior: A Deep D...
- Understanding Transformers: The Key to Electromagn...
- Understanding Transformers and Reactors: The Backb...
- Understanding Distribution Transformers: Types and...
- Understanding Transformer Fundamentals: Types and ...
- Understanding Transformer Technology: Insights and...
- Understanding SF6 Transformers: Benefits and Chall...
- Understanding Transformer Technology: Materials, D...
- Exploring Specialized Transformers: Beyond the Basics
- Understanding Transformer Design: Key Concepts and...
- Unlocking the Secrets of Transformer Engineering
- Unraveling Transformer Technology: A New Era of In...
- Unlocking Transformer Engineering: Insights from K...
- Exploring the Latest Advancements in Transformer T...
- Unraveling Transformer Engineering: Insights from ...
- Understanding Transformer Engineering: Key Insight...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Pad-Mounted Distribution Transformer...
- Understanding Submersible Transformers: Key Featur...
- Understanding Submersible Transformers: Types and ...
- Understanding Transformers: The Backbone of Electr...
- Understanding Vault Installations: The Backbone of...
- Understanding Underground Transformers: A Key Comp...
- Understanding Transformer Polarity and Standards: ...
- Understanding Operational Concerns in Transformer ...
- Understanding Transformer Connections: A Guide to ...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Configurations: A Guide ...
- Advancements in Transformer Design: From Adhesives...
- Understanding Transformer Coolants and Materials: ...
- Understanding the Evolution of Distribution Transf...
- The Evolution of Transformer Core Technology: A Lo...
- The Evolution of Distribution Transformers: From I...
- Innovations in Transformer Design: Paving the Way ...
-
▼
October
(123)