FERRORESONANCE AND DISTRIBUTION TRANSFORMER CONTRIBUTION BASIC INFORMATION
What Is The Contribution Of Distribution Transformers On Ferroresonance?
Ferroresonance is an overvoltage phenomenon that occurs when charging current for a long underground cable or other capacitive reactance saturates the core of a transformer.
Such a resonance can result in voltages as high as five times the rated system voltage, damaging lightning arresters and other equipment and possibly even the transformer itself.
When ferroresonance is occurring, the transformer is likely to produce loud squeals and groans, and the noise has been likened to the sound of steel roofing being dragged across a concrete surface.
A typical ferroresonance situation is shown in Figure 2.2.10 and consists of long underground cables feeding a transformer with a delta-connected primary.
FIGURE 2.2.10 is a typical ferroresonance situation. (From IEEE C57.105-1978, IEEE Guide for Application of Transformer Connections in Three-Phase Distribution Systems, copyright 1978 by the Institute of Electrical and Electronics Engineers, Inc. The IEEE disclaims any responsibility or liability resulting from the placement and use in the described manner. Information is reprinted with the permission of the IEEE.)
The transformer is unloaded or very lightly loaded and switching or fusing for the circuit operates one phase at a time.
Ferroresonance can occur when energizing the transformer as the first switch is closed, or it can occur if one or more distant fuses open and the load is very light. Ferroresonance is more likely to occur on systems with higher primary voltage and has been observed even when there is no cable present.
All of the contributing factors — delta or wye connection, cable length, voltage, load, single-phase switching —must be considered together. Attempts to set precise limits for prevention of the phenomenon have been frustrating.
For more on ferroresonance click the link.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
February
(28)
- POWER TRANSFORMER PROTECTIVE MAINTENANCE BASICS AN...
- TRANSFORMER OIL CONTAINMENT BASICS AND TUTORIALS
- DISTRIBUTION TRANSFORMERS HARMONICS AND DC EFFECTS...
- CAN 60 HZ TRANSFORMERS BE OPERATED AT 50 HZ? BASIC...
- TRANSFORMER PARTS STORAGE GOOD PRACTICE BASICS AND...
- TRANSFORMER MINERAL INSULATING OIL HEALTH AND ENVI...
- TRANSFORMER OILS TESTING OF NEW OIL PROPERTIES BAS...
- INRUSH CURRENT CONSIDERATION FOR TRANSFORMERS BASI...
- POWER TRANSFORMER TEMPERATURE RISE TEST AT LOAD BE...
- TRANSFORMER BUSHINGS BASICS AND TUTORIALS
- TRANSFORMER LOSSES DEFINITION BASIC AND TUTORIALS
- MATCHING TRANSFORMERS FOR PARALLEL AND BANK OPERAT...
- EFFECTS OF SHORT CIRCUITS ON TRANSFORMERS BASICS A...
- EQUIVALENT CIRCUIT OF A THREEWINDING TRANSFORMER B...
- THREE WINDING TRANSFORMER BASIC INFORMATION What I...
- ADVANTAGES AND DISADVANTAGES OF THE AUTOTRANSFORME...
- POOR POWER QUALITY (PQ) EFFECTS ON TRANSFORMERS BA...
- BUCHHOLZ RELAY OR POWER TRANSFORMER BASICS AND TUT...
- THE SCOTT TRANSFORMER CONNECTION BASIC AND TUTORIALS
- TRANSFORMING THREE-PHASE VOLTAGES INTO TWO-PHASE V...
- PAD MOUNTED TRANSFORMERS SINGLE PHASE BASIC AND TU...
- POWER TRANSFORMER IMPACT RECORDER BASICS AND TUTOR...
- SINGLE PHASE TRANSFORMER POLARITY BASICS AND TUTOR...
- FERRORESONANCE AND DISTRIBUTION TRANSFORMER CONTRI...
- ZIGZAG CONNECTION OF TRANSFORMER BASICS AND TUTORIALS
- POWER TRANSFORMERS INSULATING LIQUIDS BASICS AND T...
- DIFFERENCE BETWEEN DRY TYPE AND LIQUID FILLED TRAN...
- TRANSFORMER FAILURE MODE BASICS AND TUTORIALS
-
▼
February
(28)

No comments:
Post a Comment