POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Showing posts with label Transformer Bushing. Show all posts
Showing posts with label Transformer Bushing. Show all posts
TRANSFORMER BUSHINGS FOR SPECIAL APPLICATIONS
High-Altitude Applications
Bushings intended for application at altitudes higher than 1000 m suffer from lower air density along the outer insulator. Standards specify that, when indicated, the minimum insulation necessary at the required altitude can be determined by dividing the standard insulation length at 1000 m by the correction factor given in Table 3.2.2.
For instance, suppose that the required length of the air insulator on a bushing is 2.5 m at 1000-m altitude. Further, suppose that this bushing is to be applied at 3000 m. Hence, the air insulator must be at least 2.5/0.8 = 3.125 m in length.
The air insulator on the bushing designed for 1000 m must be replaced with a 3.125-m-long insulator, but the remainder of the bushing, i.e., the central core and the oil insulator, will remain the same as the standard bushing because these parts are not affected by air insulation. These rules do not apply to altitudes higher than 4500 m.
Highly Contaminated Environments
Insulators exposed to pollution must have adequate creep distance, measured along the external contour of the insulator, to withstand the detrimental insulating effects of contamination on the insulator surface. Figure 3.2.2 shows the undulations on the weather sheds, and additional creep distance is obtained by adding undulations or increasing their depth. Recommendations for creep distance are shown in
Table 3.2.3 according to four different classifications of contamination. For example, a 345-kV bushing has a maximum line-to-ground voltage of 220 kV, so that the minimum creep is 220 X 28 = 6160 mm for a light contamination level and 220 X 44 = 9680 mm for a heavy contamination level. The term ESDD (equivalent salt-density deposit) used in Table 3.2.3 is
TABLE 3.2.2 Dielectric-Strength Correction Factors for Altitudes
Greater than 1000 m
Altitude, m Altitude Correction Factor for Dielectric Strength
1000 1.00
1200 0.98
1500 0.95
1800 0.92
2100 0.89
2400 0.86
2700 0.83
3000 0.80
3600 0.75
4200 0.70
4500 0.67
Source: ANSI/IEEE, 1997 [1]. With permission.
TABLE 3.2.3 Recommended Creep Distances for Four Contamination Levels
Contamination Level
Equivalent Salt-Deposit
Density (ESDD), mg/cm2
Recommended Minimum Creep
Distance, mm/kV
Light 0.03–0.08 28
Medium 0.08–0.25 35
Heavy 0.25–0.6 44
Extra heavy above 0.6 54
Source: IEEE Std. C57.19.100-1995 (R1997) [8]. With permission.
the conductivity of the water-soluble deposits on the insulator surface. It is expressed in terms of the density of sodium chloride deposited on the insulator surface that will produce the same conductivity.
Following are typical environments for the four contamination levels listed:
Light-contamination areas include areas without industry and with low-density emission-producing residential heating systems, and areas with some industrial areas or residential density but with frequent winds and/or precipitation. These areas are not exposed to sea winds or located near the sea.
Medium-contamination areas include areas with industries not producing highly polluted smoke and/ or with average density of emission-producing residential heating systems, areas with high industrial and/or residential density but subject to frequent winds and/or precipitation, and areas exposed to sea winds but not located near the sea coast.
Heavy-contamination areas include those areas with high industrial density and large city suburbs with high density emission-producing residential heating systems, and areas close to the sea or exposed to strong sea winds.
Extra-heavy-contamination areas include those areas subject to industrial smoke producing thick, conductive deposits and small coastal areas exposed to very strong and polluting sea winds.
TRANSFORMER BUSHING STANDARDS REFERENCE BASIC AND TUTORIALS
TRANSFORMER BUSHING STANDARDS REFERENCE BASIC INFORMATION
What Are The IEEE Reference To Transformer Bushing
Standards?
Several bushing standards exist in the various countries
around the world. The major standards have been established by the Transformers
Committee within the IEEE Power Engineering Society and by IEC
Committee 37. Five important standards established by these
committees include the following:
1. ANSI/IEEE Std. C57.19.00, Standard Performance Characteristics
and Test Procedure for Outdoor Power Apparatus Bushings.
This is the general standard that is widely used by
countries in the Western Hemisphere and contains definitions, service
conditions, ratings, general electrical and mechanical requirements, and
detailed descriptions of routine and design test procedures for
outdoor-power-apparatus bushings.
2. IEEE Std. C57.19.01, Standard Performance Characteristics
and Dimensions for Outdoor Power Apparatus Bushings.
This standard lists the electrical-insulation and
test-voltage requirements for power-apparatus bushings rated from 15 through
800-kV maximum system voltages.
It also lists dimensions for standard-dimensioned bushings,
cantilever-test requirements for bushings rated through 345-kV system voltage,
and partial-discharge limits as well as limits for power factor and capacitance
change from before to after the standard electrical tests.
3. IEEE Std. C57.19.03, Standard Requirements, Terminology
and Test Procedures for Bushings for DC Applications [7]. This standard gives
the same type of information as ANSI/IEEE Std.
C57.19.00 for bushings for direct-current equipment,
including oil-filled converter transformers and smoothing reactors. It also
covers air-to-air dc bushings.
4. IEEE Std. C57.19.100, Guide for Application of Power
Apparatus Bushings [8]. This guide recommends practices to be used (1) for
thermal loading above nameplate rating for bushings applied on power
transformers and circuit breakers and (2) for bushings connected to isolated-phase
bus.
It also recommends practices for allowable cantilever
loading caused by the pull of the line connected to the bushing, applications
for contaminated environments and high altitudes, and maintenance practices.
5. IEC Publication 137 [9], Bushings for Alternating
Voltages above 1000 V. This standard is the IEC equivalent to the first
standard listed above and is used widely in European and Asian countries.
TRANSFORMER BUSHING INSULATION TYPES BASIC AND TUTORIALS
INSULATION OF TRANSFORMER BUSHING BASIC INFORMATION
What Are The Different Types Of Transformer Bushing
Insulation?
Another classification relates to the insulating material
used inside the bushing. In general, these materials can be used in either the
solid- or capacitance-graded construction, and in several types, more than one
of these insulating materials can be used in conjunction.
The following text gives a brief description of these types:
Air-Insulated Bushings
Air-insulated bushings generally are used only with
air-insulated apparatus and are of the solid construction that employs air at
atmospheric pressure between the conductor and the insulators.
Oil-Insulated or Oil-Filled Bushings
Oil-insulated or oil-filled bushings have electrical-grade
mineral oil between the conductor and the insulators in solid-type bushings.
This oil can be contained within the bushing, or it can be shared with the
apparatus in which the bushing is used.
Capacitance-graded bushings also use mineral oil, usually
contained within the bushing, between the insulating material and the
insulators for the purposes of impregnating the kraft paper and transferring
heat from the conducting lead.
Oil-Impregnated Paper-Insulated Bushings
Oil-impregnated paper-insulated bushings use the dielectric
synergy of mineral oil and electric grades of kraft paper to produce a
composite material with superior dielectric-withstand characteristics.
This material has been used extensively as the insulating
material in capacitance-graded cores for approximately the last 50 years.
Resin-Bonded or -Impregnated Paper-Insulated Bushings
Resin-bonded paper-insulated bushings use a resin-coated
kraft paper to fabricate the capacitance graded core, whereas resin-impregnated
paper-insulated bushings use papers impregnated with resin, which are then used
to fabricate the capacitance-graded core.
The latter type of bushing has superior dielectric
characteristics, comparable with oil-impregnated paper-insulated bushings.
Cast-Insulation Bushings
Cast-insulation bushings are constructed of a solid-cast
material with or without an inorganic filler. These bushings can be either of
the solid or capacitance-graded types, although the former type is more
representative of present technology.
Gas-Insulated Bushings
Gas-insulated bushings use pressurized gas, such as SF6 gas,
to insulate between the central conductor and the flange. It uses the same
pressurized gas as the circuit breaker, has no capacitance grading, and uses
the dimensions and placement of the ground shield to control the electric
fields.
TRANSFORMER BUSHINGS BASICS AND TUTORIALS
TRANSFORMER BUSHINGS BASIC
INFORMATION
What Are Transformer Bushing?
Functions Of Transformer Bushing?
Bushings may be classified generally by
design as follows:
a) Condenser type
1) Oil-impregnated paper insulation,
with interspersed conducting (condenser) layers or oil impregnated
paper insulation, continuously wound with interleaved lined paper
layers
2) Resin-bonded paper insulation, with
interspersed conducting (condenser layers)
b) Noncondenser type
1) Solid core or alternate layers of
solid and liquid insulation
2) Solid mass of homogeneous insulating
material (e.g., solid porcelain)
3) Gas filled
For outdoor bushings, the primary
insulation is contained in a weatherproof housing, usually porcelain.
The space between the primary insulation and the weathershed is
generally filled with an insulating oil or compound (also, plastic
and foam).
Some of the solid homogenous types may
use oil to fill the space between the conductor and the inner wall of
the weathershed. Bushings may also use gas such as SF6 as an
insulating medium between the center conductor and outer weathershed.
Bushings may be further classified
generally as being equipped or not equipped with a potential tap or
power-factor test tap or electrode. Note Potential taps are sometimes
also referred to as capacitance or voltage taps.)
The bushing, without a potential tap or
power-factor tap, is a two-terminal device that is generally tested
overall (center conductor to range) by the GST method. If the bushing
is installed in an apparatus, such as a circuit breaker, the overall
GST measurement will include all connected and energized insulating
components between the conductor and ground.
A condenser bushing is essentially a
series of concentric capacitors between the center conductor and the
ground sleeve or mounting range. A conducting layer near the ground
sleeve may be tapped and brought out to a tap terminal to provide a
three-terminal specimen.
The tapped bushing is essentially a
voltage divider and, in higher voltage designs, the tap potential may
be utilized to supply a bushing potential device for relay and other
purposes. In this design the potential tap also acts as a low-voltage
power-factor test terminal for the main bushing insulation, C1.
Modern bushings rated above 69 kV are
usually equipped with potential taps. (In some rare instances 69 kV
bushings were equipped with potential taps.) Bushings rated 69 kV and
below may be equipped with power factor taps.
In the power-factor tap design, the
ground layer of the bushing core is tapped and terminated in a
miniature bushing on the main bushing mounting range. The tap is
connected to the grounded mounting range by a screw cap on the
miniature bushing housing.
With the grounding cap removed, the tap
terminal is available as a low-voltage terminal for a UST measurement
on the main bushing insulation, C1, conductor to tapped layer.
Subscribe to:
Comments (Atom)
Previous Articles
-
▼
2025
(123)
-
▼
October
(123)
- Understanding Tensile and Compressive Forces in Wi...
- Understanding Axial Forces in Power Transformer De...
- Understanding the Dynamics of Winding Forces in El...
- Understanding Short-Circuit Forces in Power Transf...
- Understanding the Forces on Conductors in Power Tr...
- Ensuring Transformer Efficiency: Cooling Technique...
- Understanding Oil Flow and Temperature Distributio...
- Understanding Eddy Current Loss and Cooling in Pow...
- Understanding Winding Hot Spot Rise in Transformers
- Understanding Temperature Dynamics in Power Transf...
- Understanding Transformer Cooling: The Role of Dir...
- Understanding Radiator Placement and Cooling Metho...
- Understanding Transformer Cooling: The Role of Oil...
- Understanding Transformer Winding Hot Spot Factors...
- Enhancing Transformer Longevity with Natural Ester...
- Understanding Inrush Current in Transformer Operation
- Understanding Transformer Core Characteristics and...
- Understanding the Impact of Third Harmonic Voltage...
- Understanding No-Load Losses in Cold-Rolled Lamina...
- Understanding No-Load Loss in Transformer Core Design
- Understanding Transformer Design: Key Factors in E...
- Exploring the Dynamics of Steel in Transformer Cores
- Understanding Power Transformer Design: Key Concep...
- Understanding Transformer Design: Balancing Effici...
- Understanding Transformer Connections: A Primer on...
- Understanding the Winding Space Factor in Transfor...
- Understanding Load Loss and Transformer Design: A ...
- Understanding Tap Changers: Enhancing Transformer ...
- Understanding Transformer Efficiency and Voltage R...
- Understanding Transformer Impedance: Key Concepts ...
- Understanding Transformer Losses: No-Load and Load...
- Understanding Power Transformers: Insights into Th...
- Understanding Power Transformers: The Backbone of ...
- Understanding Load Losses and Impedance in Power T...
- Exploring the Intricacies of Magnetism and Sound i...
- Understanding Oil Thermal Behavior and Short-Circu...
- Understanding Insulation and Impedance in Electric...
- Understanding Transformer Insulation: Key Concepts...
- Understanding Transformer Winding Connections and ...
- Understanding Power Transformer Design Practices: ...
- Understanding the Load Loss Test in Power Transfor...
- Understanding Eddy Current Losses in Metals: A Com...
- Understanding Power Loss in Structural Components:...
- Understanding Eddy Loss in Structural Plates: A De...
- Understanding Eddy Currents and Stray Losses in Ma...
- Understanding Stray Losses in Transformers: The Ro...
- Understanding Stray Losses in Transformer Design
- Understanding Eddy Currents and Stray Losses in Po...
- Understanding Flux Density and Over-Excitation in ...
- Understanding Transformer Excitation and Losses: A...
- Understanding Core Loss in Transformers: The Role ...
- Understanding Core Losses in Magnetic Circuits: Hy...
- Understanding Core Losses in Electrical Transformers
- Understanding Zero-Sequence Impedance and Core Con...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Core Designs: A Deep Div...
- Understanding Transformer Vector Groups: A Key to ...
- Understanding Parallel Operation of Transformers: ...
- Understanding Transformer Ratings: Why Volt-Ampere...
- Understanding Transformer Circuit Parameters and E...
- Understanding Transformer Efficiency and Regulation
- Understanding Transformer Short-Circuit Testing an...
- Understanding Transformer Parameters: The Per-Unit...
- Understanding Transformer Representation in Power ...
- Understanding Core Magnetization and Losses in Tra...
- Understanding Practical Transformers: The Mechanic...
- Understanding Ideal Transformer Behavior: A Deep D...
- Understanding Transformers: The Key to Electromagn...
- Understanding Transformers and Reactors: The Backb...
- Understanding Distribution Transformers: Types and...
- Understanding Transformer Fundamentals: Types and ...
- Understanding Transformer Technology: Insights and...
- Understanding SF6 Transformers: Benefits and Chall...
- Understanding Transformer Technology: Materials, D...
- Exploring Specialized Transformers: Beyond the Basics
- Understanding Transformer Design: Key Concepts and...
- Unlocking the Secrets of Transformer Engineering
- Unraveling Transformer Technology: A New Era of In...
- Unlocking Transformer Engineering: Insights from K...
- Exploring the Latest Advancements in Transformer T...
- Unraveling Transformer Engineering: Insights from ...
- Understanding Transformer Engineering: Key Insight...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Pad-Mounted Distribution Transformer...
- Understanding Submersible Transformers: Key Featur...
- Understanding Submersible Transformers: Types and ...
- Understanding Transformers: The Backbone of Electr...
- Understanding Vault Installations: The Backbone of...
- Understanding Underground Transformers: A Key Comp...
- Understanding Transformer Polarity and Standards: ...
- Understanding Operational Concerns in Transformer ...
- Understanding Transformer Connections: A Guide to ...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Configurations: A Guide ...
- Advancements in Transformer Design: From Adhesives...
- Understanding Transformer Coolants and Materials: ...
- Understanding the Evolution of Distribution Transf...
- The Evolution of Transformer Core Technology: A Lo...
- The Evolution of Distribution Transformers: From I...
- Innovations in Transformer Design: Paving the Way ...
-
▼
October
(123)
