Two characteristics of power transformers
combine to complicate detection of internal faults with current operated relays
a)The change in magnitude of current at the
transformer terminals may be very small when a limited number of turns are
shorted within the transformer.
b)When a transformer is energized,
magnetizing inrush current that flows in one set of terminals may equal many
times the transformer rating. These and other considerations require careful
thought to obtain relay characteristics best-suited to the particular
application.
Minimum internal faults
The most difficult transformer winding
fault for which to provide protection is the fault that initially involves one
turn. A turn-to-turn fault will result in a terminal current of much less than
rated full-load current.
For example, as much as 10% of the winding
may have to be shorted to cause full-load terminal current to flow. Therefore, a single turn-to-turn fault will
result in an undetectable amount of current.
Maximum internal faults
There is no limit to the maximum internal
fault current that can flow, other than the system capability, when the fault
is a terminal fault or a fault external to the transformer but in the relay
zone. The relay system should be capable of withstanding the secondary current
of the CT on a short-time basis.
This may be a factor if the transformer is
small relative to the system fault and if the CT ratio is chosen to match the
transformer rating.
Through-faults
Fault current through a transformer is limited
by the transformer and source impedance. While current through a transformer
thus limited by its impedance can still cause incorrect relay operations or
even transformer failure, CT saturation is less likely to occur than with
unlimited currents.
No comments:
Post a Comment