Some utilities provide protection for large
high-voltage and extra-high-voltage autotransformers by using voltage-operated
bus-type high-impedance differential relays. Typical connections of this
protective system for autotransformers, with the neutral point of the wye
winding solidly grounded, are shown below.
Typical schematic
connections for high-impedance differential protection of a Y autotransformer
with unloaded tertiary
This arrangement provides protection for
all types of phase faults and ground faults, but not turn-to turn
faults. In this application, three sets of
three-phase CTs are required, one set on the high-voltage side, another set on
the low-voltage side, and the third set in the neutral ends of the winding.
This protection is immune to the effects of
magnetizing inrush current because inrush current is cancelled by the neutral
CTs. Also, there is no imbalance current in the relay circuit due to the load
tap changing equipment.
Thus a high-impedance differential relay
can be applied without any harmonic restraint, load bias, or time delay.
Autotransformers are often provided with a Δ tertiary winding. It should be
noted that with this type of scheme no protection is afforded for faults
occurring in the Δ tertiary winding.
Where the terminals for this winding are
not brought out to supply load, one corner of the Δ can be connected between
the end of one phase of the main winding and its neutral CT. This connection is
shown above.
In such an arrangement, the tertiary
winding is included in the differential protection zone, and the relay would
sense ground faults in the tertiary winding. This scheme does not provide
protection for phase faults or turn-to-turn faults in the tertiary winding.
Where the tertiary winding is used to
supply load, the Δ winding corner connection cannot be used. Hence, separate
protection is required.
Information can be found here.
No comments:
Post a Comment