TRANSFORMER CORE EARTHING BASIC INFORMATION
What Is Transformer Core Earthing?
Core earthing
Before concluding the description of core construction, mention should be made of the subject of core earthing. Any conducting metal parts of a transformer, unless solidly bonded to earth, will acquire a potential in operation which depends on their location relative to the electric field within which they lie.
In theory, the designer could insulate them from earthed metal but, in practice, it is easier and more convenient to bond them to earth. However, in adopting this alternative, there are two important requirements:
ž The bonding must ensure good electrical contact and remain secure throughout the transformer life.
ž No conducting loops must be formed, otherwise circulating currents will result, creating increased losses and/or localised overheating.
Metalwork which becomes inadequately bonded, possibly due to shrinkage or vibration, creates arcing which will cause breakdown of insulation and oil and will produce gases which may lead to Buchholz relay operation, where fitted, or cause confusion of routine gas-in-oil monitoring results y masking other more serious internal faults, and can thus be very troublesome in service.
The core and its framework represent the largest bulk of metalwork requiring to be bonded to earth. On large, important transformers, connections to core and frames can be individually brought outside the tank via 3.3 kV bushings and then connected to earth externally.
This enables the earth connection to be readily accessed at the time of initial installation on site and during subsequent maintenance without lowering the oil level for removal of inspection covers so that core insulation resistance checks can be carried out.
In order to comply with the above requirement to avoid circulating currents, the core and frames will need to be effectively insulated from the tank and from each other, nevertheless it is necessary for the core to be very positively located within the tank particularly so as to avoid movement and possible damage during transport.
It is usual to incorporate location brackets within the base of the tank in order to meet this requirement. Because of the large weight of the core and windings these locating devices and the insulation between them and the core and frames will need to be physically very substantial, although the relevant test voltage may be modest.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
March
(23)
- TRANSFORMER INRUSH EFFECTS STUDIES DOWNLOAD LINK
- DISTRIBUTION TRANSFORMER TECHNICAL SPECIFICATION E...
- TRANSFORMER TAP CHANGER DESIGN FOR MODERATE KVA AN...
- TRANSFORMER FUSING FACTOR BASIC AND TUTORIALS
- TRANSFORMER CORE EARTHING BASICS AND TUTORIALS
- THREE PHASE PAD MOUNTED TRANSFORMERS BASIC AND TUT...
- POWER TRANSFORMERS CORE IMPROVEMENT BASIC AND TUTO...
- TRANSFORMER BUSHING STANDARDS REFERENCE BASIC AND ...
- TRANSFORMER BUSHING INSULATION TYPES BASIC AND TUT...
- PARAMETERS THAT AFFECT THE DEGRADATION OF TRANSFOR...
- HVDC REACTORS APPLICATION BASIC AND TUTORIALS
- CAPACITOR INRUSH/ OUTRUSH REACTORS BASIC AND TUTOR...
- CONSTANT VOLTAGE TRANSFORMER BASICS AND TUTORIALS
- POLARITY TEST OF SINGLE PHASE TRANSFORMER BASIC AN...
- FACTORS AFFECTING DRY TYPE TRANSFORMER'S LIFE BASI...
- ROGOWSKI COILS BASICS AND TUTORIALS
- DRY TYPE TRANSFORMERS BASICS AND TUTORIALS
- TRANSFORMER HEATING BASICS AND TUTORIALS
- PUBLIC RESPONSE TO TRANSFORMER AUDIBLE SOUND BASIC...
- POWER TRANSFORMER AUTOMATIC CONTROL FOR TAP CHANGE...
- DESIGN OF POWER TRANSFORMERS INSULATION STRUCTURES...
- POWER TRANSFORMERS IN SERVICE TESTING BASIC AND TU...
- POWER TRANSFORMER TAP CHANGERS BASIC AND TUTORIALS
-
▼
March
(23)
No comments:
Post a Comment