TECHNICAL SPECIFICATIONS OF DISTRIBUTION TRANSFORMER LINKS
Technical Specifications Distribution Transformer
DISTRIBUTION TRANSFORMER SAMPLE SPECS FROM INDIA
2.1 All equipment and material shall be designed manufactured and tested in accordance with the latest applicable Indian Standard. IEC standard and CBIP manuals except where modified and / or supplemented this specification.
2.2. Equipment and material confirming to any other standard, which ensures equal or better quality, may be accepted. In such case copies of English version of the standard adopted shall be submitted.
2.3. The Transformer offered shall in general comply with the latest issues including amendments of the following Indian standards but not restricted to it.
3. System Description:
The distribution transformers shall be installed at outdoor/indoor location along 11 kV distribution networks, which consists of both underground and overhead network. The HV winding would be connected to SFU/OCB/VCB of the ring main unit through 11 kV (E) XLPE/PILC cable. LV winding would be connected to switch type Fuse section pillar through 1.1 kV 1c, 400 sq mm XLPE cable.
4. Design Criteria:
4.1. The transformers shall be installed in hot, humid tropical atmosphere. All equipment accessories and wiring shall be provided with tropical finish to prevent fungus growth..
4.2. The transformers shall be capable of continuous operation of rated output under the operating conditions of voltage and frequency variations as per statutory limits governed by relevant Indian Standard and Electricity Act-2003 and its amendments in force.
4.3. The transformer shall conform to best engineering practice.
4.4. The design material construction shall be such that to secure reliability, economy, safe and convenient operation and shall include all specified or unspecified incidental items necessary for similar equipment for convenient working in every respect.
4.5. The transformers shall be capable of withstanding the short circuit stresses due to terminal fault between phase to phase and phase to ground on one winding with full voltage maintained on the other windings for a minimum period of three seconds.
4.6. The transformers shall be free from annoying hum or vibration. The design shall be such as not to cause any undesirable interference with radio or communication circuits.
4.7. Atmospheric Condition: The equipment offered shall be suitable for continuous satisfactory operation in following prevailing climatic conditions.
DOWNLOAD THE COMPLETER DOCUMENT HERE!!!
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
March
(23)
- TRANSFORMER INRUSH EFFECTS STUDIES DOWNLOAD LINK
- DISTRIBUTION TRANSFORMER TECHNICAL SPECIFICATION E...
- TRANSFORMER TAP CHANGER DESIGN FOR MODERATE KVA AN...
- TRANSFORMER FUSING FACTOR BASIC AND TUTORIALS
- TRANSFORMER CORE EARTHING BASICS AND TUTORIALS
- THREE PHASE PAD MOUNTED TRANSFORMERS BASIC AND TUT...
- POWER TRANSFORMERS CORE IMPROVEMENT BASIC AND TUTO...
- TRANSFORMER BUSHING STANDARDS REFERENCE BASIC AND ...
- TRANSFORMER BUSHING INSULATION TYPES BASIC AND TUT...
- PARAMETERS THAT AFFECT THE DEGRADATION OF TRANSFOR...
- HVDC REACTORS APPLICATION BASIC AND TUTORIALS
- CAPACITOR INRUSH/ OUTRUSH REACTORS BASIC AND TUTOR...
- CONSTANT VOLTAGE TRANSFORMER BASICS AND TUTORIALS
- POLARITY TEST OF SINGLE PHASE TRANSFORMER BASIC AN...
- FACTORS AFFECTING DRY TYPE TRANSFORMER'S LIFE BASI...
- ROGOWSKI COILS BASICS AND TUTORIALS
- DRY TYPE TRANSFORMERS BASICS AND TUTORIALS
- TRANSFORMER HEATING BASICS AND TUTORIALS
- PUBLIC RESPONSE TO TRANSFORMER AUDIBLE SOUND BASIC...
- POWER TRANSFORMER AUTOMATIC CONTROL FOR TAP CHANGE...
- DESIGN OF POWER TRANSFORMERS INSULATION STRUCTURES...
- POWER TRANSFORMERS IN SERVICE TESTING BASIC AND TU...
- POWER TRANSFORMER TAP CHANGERS BASIC AND TUTORIALS
-
▼
March
(23)
No comments:
Post a Comment