CURRENT TRANSFORMER (CT GROUNDING) BASIC INFORMATION



IEEE standard C57.13.3 serves as the ANSI guide to standardize instrument transformer grounding practices. The grounding of CTs is important to both safety and the correct operation of protective relays.

To assure safe and reliable operation, the neutral of the CT secondary should have a single ground location for each circuit. The single ground is irrespective of the number of CTs or the chosen grounding location.

Utilizing a single ground eliminates the risk of redundant ground loops and associated problems.

During normal operation more than one ground on a CT circuit is not an obvious problem, other than the difficulties it may cause during testing. However, during a fault condition, multiple grounds allow a different ground potential rise for each CT.

The result is a significant current flow through the CT circuit that is not representative of the primary current. This ground loop typically creates a potential across the operating coil of the differential relay, causing the relay to pick up as though a fault exists in the relay’s protective zone.

Tripping a differential relay due to a fault external to the zone of protection is one of the more frequent nuisance trips. These nuisance trips may not only shut down the load but may require a maintenance crew to spend days testing to determine that no real problem exists in the differential zone.

Further, the actual problem may go undiscovered until the system is re-energized into the original fault.


To demonstrate what happens with a second ground on the CT circuit, refer to Figure 1. Figure 1 shows a typical differential relay with two CTs per phase. The recommended method of grounding is to install a single ground point at the first point of application (switchboard or relay panel) of the CT secondary circuit.

In the case of a fault internal to the protective zone, the voltage developed by the CTs is of the same polarity. The magnitude of voltage drop across the operating coil is sufficient to operate the relay.

A second ground is on a CT mounted near where a ground fault occurs. If the fault creates a ground potential rise of 100 volts, the protective relay will experience sufficient voltage across the operating coil to cause the relay to nuisance trip even though the fault was outside the fault zone
.
Just as with any other event, there is an exception to this standard. Many of the new multifunction relays (ABB, Schweitzer, GE/Multilin, and Basler) are designed to connect all CTs coming into the relay in a wye connection. Each wye has to be grounded.

The most desirable way to do this is to bus the wye points together at the relay panel and have a single conductor to ground to make certain the relay has but one ground potential.

No comments:

Post a Comment

Related Posts Plugin for WordPress, Blogger...

TOP COUNTRIES