Basic Conditions
1. The basic loading of a transformer for normal life expectancy is continuous loading at rated output when operated under normal service conditions.
It is assumed that operation under these conditions is equivalent to operation in a continuous ambient temperature of 30 C for cooling air or 25 C for cooling water.
Normal life expectancy will result from operating with a continuous hottest-spot conductor temperature of 110 C (or equivalent variable temperature with 120 C maximum) in any 24-h period.
2. The hottest-spot conductor temperature determines loss of life due to loading. This temperature cannot be directly measured on commercial designs because of voltage hazard when placing a temperature detector at the proper location.
The hottest-spot allowances are based on tests of laboratory models.
3. The hottest-spot temperature at rated load is usually taken as the sum of the average winding temperature and a 15 C allowance2 for hottest spot.
For mineral oil-immersed transformers operating continuously under the foregoing conditions with normal life expectancy, this temperature has been assumed to be a maximum of 110 C.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
June
(17)
- BASIC LOADING OF POWER TRANSFORMER BASIC INFORMATION
- INSULATION CLASSES OF POWER TRANSFORMER BASIC INFO...
- OIL IMMERSED TRANSFORMER INSULATION VALUE BASIC AN...
- DISTRIBUTION TRANSFORMER TYPES BASIC AND TUTORIALS
- BOOSTER TRANSFORMERS CONNECTION & OPERATION BASIC ...
- DELTA, STAR, AND OPEN DELTA TRANSFORMER CONNECTION...
- CONSTANT CURRENT TRANSFORMER BASIC OPERATION TUTOR...
- THREE PHASE TRANSFORMER APPLICATION BASIC AND TUTO...
- POWER TRANSFORMER INSULATION CLASS SYSTEM BASIC AN...
- TRANSFORMER CLASSIFICATION BASIC AND TUTORIALS
- CALCULATING TRANSFORMER LOSS OF LIFE BASIC AND TUT...
- DIFFERENT TYPES OF TRANSFORMER PROTECTION BASIC IN...
- ADVANCED VOLTAGE AND CURRENT TRANSDUCERS BASIC INF...
- MEASUREMENT OF TRANSFORMER NO LOAD LOSSES BASIC IN...
- ANGULAR DISPLACEMENT OF THREE PHASE TRANSFORMERS B...
- TRANSFORMER BUSHINGS FOR SPECIAL APPLICATIONS
- POWER TRANSFORMER WATER IN OIL ANALYSIS BASIC AND ...
-
▼
June
(17)
No comments:
Post a Comment