Basic Conditions
1. The basic loading of a transformer for normal life expectancy is continuous loading at rated output when operated under normal service conditions.
It is assumed that operation under these conditions is equivalent to operation in a continuous ambient temperature of 30 C for cooling air or 25 C for cooling water.
Normal life expectancy will result from operating with a continuous hottest-spot conductor temperature of 110 C (or equivalent variable temperature with 120 C maximum) in any 24-h period.
2. The hottest-spot conductor temperature determines loss of life due to loading. This temperature cannot be directly measured on commercial designs because of voltage hazard when placing a temperature detector at the proper location.
The hottest-spot allowances are based on tests of laboratory models.
3. The hottest-spot temperature at rated load is usually taken as the sum of the average winding temperature and a 15 C allowance2 for hottest spot.
For mineral oil-immersed transformers operating continuously under the foregoing conditions with normal life expectancy, this temperature has been assumed to be a maximum of 110 C.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
INSULATION CLASSES OF POWER TRANSFORMER BASIC INFORMATION AND TUTORIALS
The type of insulation used in dry-type–transformer design and construction has a definite bearing on the size and operating temperature of the unit. Currently four classes of insulation, each having a separate NEMA specification and temperature limit, are being used.
A look at these will facilitate selection of the proper unit to meet prescribed installation and operating conditions.
1. Class 130 insulation-system transformers. When properly applied and loaded in an ambient not over 40 C, these transformers will operate at not more than a 60 C temperature rise on the winding.
These units can be used as control-type transformers when higher temperatures might affect other temperature-sensitive devices in the enclosure or as distribution transformers in locations (textile mills, sawmills, etc.) where combustible flyings might be present in the surrounding atmosphere.
2. Class 150 insulation-system transformers. These units have a higher-temperature insulating system and are physically smaller and about half the weight of Class A units of corresponding rated capacities. When properly loaded to rated kilovolt-amperes and installed in an ambient not over 40 C,
Class 150 units will operate at a maximum 80 C rise on the winding. For years dry-type distribution transformers have been of the Class 150 type.
3. Class 200 insulation-system transformers. These units also have a high-temperature insulating system and, when properly loaded and applied in an ambient not over 40 C, will operate at no more than 130 C rise on the winding.
The units are smaller in size than similarly rated Class 150 units and currently are available from a number of manufacturers in ratings of 25 kVA and lower, both single- and three-phase design. One manufacturer designs in-wall, flush-mounted dry-type transformers as Class 200 units.
4. Class 220 insulation-system transformers. These units are insulated with a high temperature system of glass, silicone, and asbestos components and are probably the most compact ones available.
When properly loaded and applied in an ambient not over 40 C, Class 220 transformers will operate at a maximum 150 C rise on the winding. This class of insulation is used primarily in designs in which the core and coil are completely enclosed in a ventilated housing.
Generally, this stipulation covers units with ratings of 30 kVA and larger. Some experts recommend that the hottest spot on the metal enclosure be limited to a maximum rise of 40 C above a 40 C ambient. It should be noted that Class 150 insulation is being replaced with Class 200 or 220 insulation in transformers of recent design.
Another significant factor which concerns all dry-type transformers is that they should never be overloaded. The way to avoid this is to size the primary or secondary overcurrent device as close as possible to the full-load primary or secondary current for other than motor loads.
If close overcurrent protection has not been provided, loads should be checked periodically. Overloading a transformer causes excessive temperature, which, in turn, produces overheating. This results in rapid deterioration of the insulation and will cause complete failure of the transformer coils.
A look at these will facilitate selection of the proper unit to meet prescribed installation and operating conditions.
1. Class 130 insulation-system transformers. When properly applied and loaded in an ambient not over 40 C, these transformers will operate at not more than a 60 C temperature rise on the winding.
These units can be used as control-type transformers when higher temperatures might affect other temperature-sensitive devices in the enclosure or as distribution transformers in locations (textile mills, sawmills, etc.) where combustible flyings might be present in the surrounding atmosphere.
2. Class 150 insulation-system transformers. These units have a higher-temperature insulating system and are physically smaller and about half the weight of Class A units of corresponding rated capacities. When properly loaded to rated kilovolt-amperes and installed in an ambient not over 40 C,
Class 150 units will operate at a maximum 80 C rise on the winding. For years dry-type distribution transformers have been of the Class 150 type.
3. Class 200 insulation-system transformers. These units also have a high-temperature insulating system and, when properly loaded and applied in an ambient not over 40 C, will operate at no more than 130 C rise on the winding.
The units are smaller in size than similarly rated Class 150 units and currently are available from a number of manufacturers in ratings of 25 kVA and lower, both single- and three-phase design. One manufacturer designs in-wall, flush-mounted dry-type transformers as Class 200 units.
4. Class 220 insulation-system transformers. These units are insulated with a high temperature system of glass, silicone, and asbestos components and are probably the most compact ones available.
When properly loaded and applied in an ambient not over 40 C, Class 220 transformers will operate at a maximum 150 C rise on the winding. This class of insulation is used primarily in designs in which the core and coil are completely enclosed in a ventilated housing.
Generally, this stipulation covers units with ratings of 30 kVA and larger. Some experts recommend that the hottest spot on the metal enclosure be limited to a maximum rise of 40 C above a 40 C ambient. It should be noted that Class 150 insulation is being replaced with Class 200 or 220 insulation in transformers of recent design.
Another significant factor which concerns all dry-type transformers is that they should never be overloaded. The way to avoid this is to size the primary or secondary overcurrent device as close as possible to the full-load primary or secondary current for other than motor loads.
If close overcurrent protection has not been provided, loads should be checked periodically. Overloading a transformer causes excessive temperature, which, in turn, produces overheating. This results in rapid deterioration of the insulation and will cause complete failure of the transformer coils.
Subscribe to:
Comments (Atom)
Previous Articles
-
▼
2025
(123)
-
▼
October
(123)
- Understanding Tensile and Compressive Forces in Wi...
- Understanding Axial Forces in Power Transformer De...
- Understanding the Dynamics of Winding Forces in El...
- Understanding Short-Circuit Forces in Power Transf...
- Understanding the Forces on Conductors in Power Tr...
- Ensuring Transformer Efficiency: Cooling Technique...
- Understanding Oil Flow and Temperature Distributio...
- Understanding Eddy Current Loss and Cooling in Pow...
- Understanding Winding Hot Spot Rise in Transformers
- Understanding Temperature Dynamics in Power Transf...
- Understanding Transformer Cooling: The Role of Dir...
- Understanding Radiator Placement and Cooling Metho...
- Understanding Transformer Cooling: The Role of Oil...
- Understanding Transformer Winding Hot Spot Factors...
- Enhancing Transformer Longevity with Natural Ester...
- Understanding Inrush Current in Transformer Operation
- Understanding Transformer Core Characteristics and...
- Understanding the Impact of Third Harmonic Voltage...
- Understanding No-Load Losses in Cold-Rolled Lamina...
- Understanding No-Load Loss in Transformer Core Design
- Understanding Transformer Design: Key Factors in E...
- Exploring the Dynamics of Steel in Transformer Cores
- Understanding Power Transformer Design: Key Concep...
- Understanding Transformer Design: Balancing Effici...
- Understanding Transformer Connections: A Primer on...
- Understanding the Winding Space Factor in Transfor...
- Understanding Load Loss and Transformer Design: A ...
- Understanding Tap Changers: Enhancing Transformer ...
- Understanding Transformer Efficiency and Voltage R...
- Understanding Transformer Impedance: Key Concepts ...
- Understanding Transformer Losses: No-Load and Load...
- Understanding Power Transformers: Insights into Th...
- Understanding Power Transformers: The Backbone of ...
- Understanding Load Losses and Impedance in Power T...
- Exploring the Intricacies of Magnetism and Sound i...
- Understanding Oil Thermal Behavior and Short-Circu...
- Understanding Insulation and Impedance in Electric...
- Understanding Transformer Insulation: Key Concepts...
- Understanding Transformer Winding Connections and ...
- Understanding Power Transformer Design Practices: ...
- Understanding the Load Loss Test in Power Transfor...
- Understanding Eddy Current Losses in Metals: A Com...
- Understanding Power Loss in Structural Components:...
- Understanding Eddy Loss in Structural Plates: A De...
- Understanding Eddy Currents and Stray Losses in Ma...
- Understanding Stray Losses in Transformers: The Ro...
- Understanding Stray Losses in Transformer Design
- Understanding Eddy Currents and Stray Losses in Po...
- Understanding Flux Density and Over-Excitation in ...
- Understanding Transformer Excitation and Losses: A...
- Understanding Core Loss in Transformers: The Role ...
- Understanding Core Losses in Magnetic Circuits: Hy...
- Understanding Core Losses in Electrical Transformers
- Understanding Zero-Sequence Impedance and Core Con...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Core Designs: A Deep Div...
- Understanding Transformer Vector Groups: A Key to ...
- Understanding Parallel Operation of Transformers: ...
- Understanding Transformer Ratings: Why Volt-Ampere...
- Understanding Transformer Circuit Parameters and E...
- Understanding Transformer Efficiency and Regulation
- Understanding Transformer Short-Circuit Testing an...
- Understanding Transformer Parameters: The Per-Unit...
- Understanding Transformer Representation in Power ...
- Understanding Core Magnetization and Losses in Tra...
- Understanding Practical Transformers: The Mechanic...
- Understanding Ideal Transformer Behavior: A Deep D...
- Understanding Transformers: The Key to Electromagn...
- Understanding Transformers and Reactors: The Backb...
- Understanding Distribution Transformers: Types and...
- Understanding Transformer Fundamentals: Types and ...
- Understanding Transformer Technology: Insights and...
- Understanding SF6 Transformers: Benefits and Chall...
- Understanding Transformer Technology: Materials, D...
- Exploring Specialized Transformers: Beyond the Basics
- Understanding Transformer Design: Key Concepts and...
- Unlocking the Secrets of Transformer Engineering
- Unraveling Transformer Technology: A New Era of In...
- Unlocking Transformer Engineering: Insights from K...
- Exploring the Latest Advancements in Transformer T...
- Unraveling Transformer Engineering: Insights from ...
- Understanding Transformer Engineering: Key Insight...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Pad-Mounted Distribution Transformer...
- Understanding Submersible Transformers: Key Featur...
- Understanding Submersible Transformers: Types and ...
- Understanding Transformers: The Backbone of Electr...
- Understanding Vault Installations: The Backbone of...
- Understanding Underground Transformers: A Key Comp...
- Understanding Transformer Polarity and Standards: ...
- Understanding Operational Concerns in Transformer ...
- Understanding Transformer Connections: A Guide to ...
- Understanding Single-Phase and Three-Phase Transfo...
- Understanding Transformer Configurations: A Guide ...
- Advancements in Transformer Design: From Adhesives...
- Understanding Transformer Coolants and Materials: ...
- Understanding the Evolution of Distribution Transf...
- The Evolution of Transformer Core Technology: A Lo...
- The Evolution of Distribution Transformers: From I...
- Innovations in Transformer Design: Paving the Way ...
-
▼
October
(123)