When a transformer is energized with no load, the secondary voltage will be exactly the primary voltage divided by the turns ratio (NP/NS). When the transformer is loaded, the secondary voltage will be diminished by an amount determined by the transformer impedance and the power factor of the load.
This change in voltage is called regulation and is actually defined as the rise in voltage when the load is removed. One result of the definition of regulation is that it is always a positive number.
The primary voltage is assumed to be held constant at the rated value during this process. The exact calculation of percent regulation is given in Equation
where cos is the power factor of the load and L is per unit load on the transformer.
The most significant portion of this equation is the cross products, and since %X predominates over %R in the transformer impedance and cos predominates over sin for most loads, the percent regulation is usually less than the impedance (at L = 1).
When the power factor of the load is unity, then sin is zero and regulation is much less than the transformer impedance.
A much simpler form of the regulation calculation is given in Equation
For typical values, the result is the same as the exact calculation out to the fourth significant digit or so.
POWER TRANSFORMER | DISTRIBUTION TRANSFORMER | TRANSFORMER DESIGN | TRANSFORMER PRINCIPLES | TRANSFORMER THEORY | TRANSFORMER INSTALLATION | TRANSFORMER TUTORIALS
Subscribe to:
Post Comments (Atom)
Previous Articles
-
▼
2012
(166)
-
▼
May
(17)
- IMPEDANCE MATCHING TRANSFORMER SELECTION BASIC AND...
- RESISTANCE TYPE TRANSFORMER LOAD TAP CHANGER BASICS
- INSTRUMENT TRANSFORMER METERING IN METALCLAD SWITC...
- TYPES OF FAILURES IN POWER TRANSFORMERS BASIC AND ...
- THE NATURE OF TRANSFORMER LOSSES BASIC INFORMATION
- AUTOTRANSFORMER CONNECTIONS BASIC AND TUTORIALS
- POWER TRANSFORMER TEMPERATURE RISE AND THE THERMAL...
- POWER TRANSFORMER SERIES IMPEDANCE AND REGULATION ...
- ON LOAD TAP CHANGER DESIGN TEST FOR MOTOR DRIVEN M...
- ON LOAD TAP CHANGER NAMEPLATE SAMPLE AND REQUIREMENTS
- TESTING OF PHASE SHIFTING TRANSFORMERS BASIC AND T...
- PHASE SHIFTING TRANSFORMER USUAL SERVICE CONDITION...
- TRANSFORMER PERCENT (%) REGULATION BASIC AND TUTOR...
- TRANSFORMERS TAPPING BASICS AND TUTORIALS
- 50 MVA 138KV AUTOTRANSFORMER SPECIFICATION SAMPLE
- HIGH PERMEABILITY STEEL USED IN TRANSFORMER CORE B...
- OPEN DELTA CONNECTION FOR LIGHT AND POWER BASIC AN...
-
▼
May
(17)

No comments:
Post a Comment