THREE (3) PHASE TO THREE (3) PHASE CONVERSION BASIC INFORMATION AND TUTORIALS


The delta-delta, the delta-Y, and the Y-Y connections are the most generally used; they are illustrated in figure below. The Y-delta and delta-delta connections may be used as step-up transformers for moderate voltages.

  
                      Standard 3-phase/3-phase transformer systems.
The Y-delta has the advantage of providing a good grounding point on the Y-connected side which does not shift with unbalanced load and has the further advantage of being free from third-harmonic voltages and currents; the delta-delta has the advantage of permitting operation in V in case of damage to one of the units.

Delta connections are not the best for transmission at very high voltage; they may, however, be associated at some point with other connections that provide  means for properly grounding the high voltage system; but it is better, on the whole, to avoid mixed systems of connections. The delta-Y step-up and Y-delta step-down connections are without question the best for high voltage transmission systems.

They are economical in cost, and provide a stable neutral whereby the high-voltage system may be directly grounded or grounded through resistance of such value as to damp the system critically and prevent the possibility of oscillation.

The Y-Y connection (or Y-connected autotransformer) may be used to interconnect two delta systems and provide suitable neutrals for grounding both of them. A Y-connected autotransformer may be used to interconnect two Y systems which already have neutral grounds, for reasons of economy.

In either case, a delta-connected tertiary winding is frequently provided for one or more of the following purposes. In stabilization of the neutral, if a Y-connected transformer (or autotransformer) with a delta connected tertiary is connected to an ungrounded delta system (or poorly grounded Y system), stability of the system neutral is increased.

That is, a single-phase short-circuit to ground on the transmission line will cause less drop in voltage on the short-circuited phase and less rise in voltage on the other two phases. A 3-phase three-leg Y-connected transformer without delta tertiary furnishes very little stabilization of the neutral, and the delta tertiary is generally needed.

Other Y connections offer no stabilization of the neutral without a delta tertiary. With increased neutral stabilization, the fault current in the neutral on single-phase short circuit is increased, and this may be needed for improved relay protection of the system.

Third-harmonic components of exciting current find a relatively low impedance path in a delta tertiary on a Y-connected transformer, and less of the third-harmonic exciting current appears in the connected transmission lines, where it might cause interference with communication circuits. Failure to provide a path for third-harmonic current in Y-connected 3-phase shell-type transformers or banks of single-phase transformers will result in excessive third-harmonic voltage from line to neutral.

The bank of a 3-phase, three-legged core-type Y-connected transformer acts as a delta winding with high impedance to the other windings. As a consequence, there is very little third-harmonic line-to-neutral voltage and a separate delta tertiary is not needed to reduce it. An external load can be supplied from a delta tertiary. This may include synchronous or static capacitors to improve system operating conditions.

PHASE ANGLE CONTROL TRANSFORMERS BASIC INFORMATION AND TUTORIALS


Tap-changing equipment is sometimes used in a loop system, for phase-angle control, for the purpose of obtaining minimum losses in the loop due to unequal impedances in the various portions of the circuit.

Transformers used to derive phase-angle control do not differ materially, either mechanically or electrically, from those used for in phase control. In general, phase-angle control is obtained by interconnecting the phases, that is, by deriving a voltage from one phase and inserting it in another.

The simple arrangement given in figure below illustrates a single core delta-connected autotransformer in which the series windings are so interconnected as to introduce into the line a quadrature voltage.

One phase only is printed in solid lines so as to show more clearly how the quadrature voltage is obtained. The terminals of the common winding are connected to the midpoints of the series winding in order that the in phase voltage ratio between the primary lines ABC and secondary lines XYZ is unity for all values of phase angle introduced between them.

As large high-voltage systems have become extensively interconnected, a need has developed to control the transfer of real power between systems by means of phase-angle-regulating transformers.

The most commonly used circuit for this purpose is the two-core, four-winding arrangement. The high-voltage common winding is Y-connected, with reduced insulation at the neutral for economy of design, and a series transformer is employed so that low-voltage-switching equipment may be used.


Phase-shifting regulating transformers; single core delta-connected common winding for low-voltage systems.

Previous Articles