TRANSFORMER GAS IN OIL ANALYSIS BASIC INFORMATION AND TUTORIALS


Various research organizations, such as Westinghouse Electric Corporation, Analytical Associates, Inc., that did extensive research in the 1970s quickly led to the widespread use of dissolved gas-in-oil analysis as a predictive maintenance tool [4]. There is also an extensive bibliography on this subject found in IEEE Std. C57.104–1991 [5].

The basic theory is straightforward: Transformer dielectric fluids are refined from petroleum and are very complex mixtures containing aromatic, naphthenic, and paraffinic hydrocarbons. At high temperatures, some of these molecules break down into hydrogen plus small hydrocarbon molecules such as, methane, ethane, ethylene, acetylene, propane, and propylene. This process is known as cracking.

The kraft paper materials that are used to insulate transformer windings are made up of cellulose. At high temperatures, cellulose oxidizes to form carbon dioxide (CO2), carbon monoxide (CO) and water (H2O). High concentrations of CO2 and or CO are indications of overheated windings.

All of the breakdown products are gases that dissolve readily in transformer oil in different concentrations, depending on the specific gas and the temperatures that produce them. By taking samples of transformer insulating oil, extracting the dissolved gases and doing a quantitative analysis of the various gases in the samples through gas chromatography, it is possible to infer the temperatures at the sites where these gases were produced.

At temperatures below 150°C, transformer oil starts breaking down into methane (CH4) and ethane (C2H6). At temperatures above 150°C, ethylene (C2H4) begins to be produced in large quantities while the concentration of ethane decreases.

At around 600°C, the ethylene production peaks while the concentration of methane continues to increase. Acetylene (C2H2) production starts at around 600°C and methane concentration peaks at 1000°C. Hydrogen (H2) production is not significant below 700°C and continues to increase along with acetylene at temperatures above 1400°C.

Therefore, the relative concentrations of the key gases change over a wide range of temperature. This is basis for the application of dissolved gas in-oil analysis for predictive and diagnostic use. An approximate formula uses the ratio of C2H4/C2H6 to derive the temperature of oil decomposition between 300°C and 800°C:

T(°C) = 100 C2H4/C2H6 + 150

The so-called Rogers ratio method takes the ratios of several key gases into account to develop a code that is supposed to give an indication of what is causing the evolution of gas. The codes for the four ratio method are given in Table 8.2. A fairly detailed diagnosis of transformer trouble can be derived from various combinations of codes, shown in Table 8.3.



The diagnoses shown above were derived from empirical observation. The problem with the four-ratio Rogers code is that a code generated from the gas concentrations will often not match any of the ‘‘known’’ diagnoses.

So like a rare disease with strange symptoms, many cases of transformer trouble cannot be diagnosed at all using this method. Another method, called the three-ratio method, sometimes works when the four-ratio method does not.

In the three-ratio method, the values of A, B, and C are given in Table 8.4 with the corresponding diagnoses for the various combinations given in Table 8.5. Not only are the ratios of the key gases important, but the total quantity of dissolved gas and the rate of increase are also important factors in making a diagnosis. One of the criteria for making a judgment call is the total combustible gas concentration. The combustible gases include H2, CH4,


C2H4, C2H6, C2H2, which are produced by oil decomposition, and CO, which is produced by cellulose decomposition. Each utility has a different philosophy and a different threshold for concern.


Table 8.6 gives one set of guidelines based on good utility practice that is useful for determining the overall health of a power transformer based on the total concentration of combustible gases.

It is generally accepted that if the rate of combustible gas generation exceeds 100 ppm per day on a continuing basis, or if the presence of C2H2 exceeds 20 ppm, then consideration should be given to taking the transformer out of service to perform additional tests and inspection.

IEEE Std. C57.104-1991 Table 3 also provides a set of actions based on the total dissolved combustible gas (TDCG) concentrations as well as the daily rate of TDCG production.

According to the IEEE Guide, a rate of 30 ppm per day is the threshold for considering removing the transformer from service. Oil samples are taken from the bottom drain valve in a sealed syringe to prevent the dissolved gases from escaping.

The samples are sent to a chemical laboratory where the dissolved gases are extracted from the sample under vacuum and analyzed using a gas chromatograph. The results are reported as ppm dissolved in oil.

  


PARALLEL OPERATIONS OF TRANSFORMER PRIMER INFORMATION


The theoretically ideal conditions for paralleling transformers are:

1. Identical turn ratios and voltage ratings.

2. Equal percent impedances.

3. Equal ratios of resistance to reactance.

4. Same polarity.

5. Same phase angle shift.

6. Same phase rotation.

Single-Phase Transformers
For single-phase transformers, only the first four conditions apply, as there is no phase rotation or phase angle shift due to voltage transformation.

If the turns ratio are not same a circulating current will flow even at no load. If the percent impedance or the ratios of resistance to reactance are different there will be no circulating current at no load, but the division of load between the transformers when applied will no longer be proportional to their KVA ratings.

Three-Phase Transformers
The same conditions hold true for three phase transformers except that in this case the question of phase rotation and phase angle shift must be considered.

Phase Angle Shift
Certain transformer connections as the wye-delta or wye-zigzag produce a 30ยบ shift between the line voltages on the primary side and those on the secondary side. Transformers with these connections cannot be paralleled with other transformers not having this shift such as wye-wye, delta-delta, zigzag-delta, or zigzag-zigzag.

Phase Rotation
Phase rotation refers to the order in which the terminal voltages reach their maximum values. In paralleling, those terminals whose voltage maximums occur simultaneously are paired.
Power Transformer Practice

The preceding discussion covered the theoretically ideal requirements for paralleling. In actual practice, good paralleling can be accomplished although the actual transformer conditions deviate by small percentages from the theoretical ones.

Good paralleling is considered attainable when the percentage impedances of two winding transformers are within 7.5% of each other. For multi-winding and auto-transformers, the generally accepted limit is 10%.

Furthermore, in power transformers of normal design the ratio of resistance to reactance is generally sufficiently small to make the requirement of equal ratios of negligible importance in paralleling.

When it is desired to parallel transformers having widely different impedances, reactors or auto-transformers having the proper ratio should be used. If a reactor is used it is placed in series with the transformer whose impedance is lower. It should have a value sufficient to bring the total effective percent impedance of the transformer plus the reactor up to the value of the percent impedance of the second transformer.

When an auto-transformer is used, the relative currents supplied by each transformer are determined by the ratio of the two sections of the auto-transformer. The auto-transformer adds a voltage to the voltage drop in the transformer with the lower impedances and subtracts a voltage from the voltage drop in the transformer with the higher impedance. Auto-transformers for use in paralleling power transformers are specially designed for each installation. The wiring diagram showing the method of connecting the auto-transformer is usually furnished.

In general, transformers built to the same manufacturing specifications as indicated by the nameplate may be operated in parallel.

Connecting transformers in parallel when the low voltage tension is comparatively low requires care that the corresponding connecting bars or conductors have approximately the same impedance. If they do not, the currents will not divide properly.

Information Courtesy of ABB Power Transformers

Previous Articles