PARALLEL OPERATIONS OF TRANSFORMER PRIMER INFORMATION


The theoretically ideal conditions for paralleling transformers are:

1. Identical turn ratios and voltage ratings.

2. Equal percent impedances.

3. Equal ratios of resistance to reactance.

4. Same polarity.

5. Same phase angle shift.

6. Same phase rotation.

Single-Phase Transformers
For single-phase transformers, only the first four conditions apply, as there is no phase rotation or phase angle shift due to voltage transformation.

If the turns ratio are not same a circulating current will flow even at no load. If the percent impedance or the ratios of resistance to reactance are different there will be no circulating current at no load, but the division of load between the transformers when applied will no longer be proportional to their KVA ratings.

Three-Phase Transformers
The same conditions hold true for three phase transformers except that in this case the question of phase rotation and phase angle shift must be considered.

Phase Angle Shift
Certain transformer connections as the wye-delta or wye-zigzag produce a 30ยบ shift between the line voltages on the primary side and those on the secondary side. Transformers with these connections cannot be paralleled with other transformers not having this shift such as wye-wye, delta-delta, zigzag-delta, or zigzag-zigzag.

Phase Rotation
Phase rotation refers to the order in which the terminal voltages reach their maximum values. In paralleling, those terminals whose voltage maximums occur simultaneously are paired.
Power Transformer Practice

The preceding discussion covered the theoretically ideal requirements for paralleling. In actual practice, good paralleling can be accomplished although the actual transformer conditions deviate by small percentages from the theoretical ones.

Good paralleling is considered attainable when the percentage impedances of two winding transformers are within 7.5% of each other. For multi-winding and auto-transformers, the generally accepted limit is 10%.

Furthermore, in power transformers of normal design the ratio of resistance to reactance is generally sufficiently small to make the requirement of equal ratios of negligible importance in paralleling.

When it is desired to parallel transformers having widely different impedances, reactors or auto-transformers having the proper ratio should be used. If a reactor is used it is placed in series with the transformer whose impedance is lower. It should have a value sufficient to bring the total effective percent impedance of the transformer plus the reactor up to the value of the percent impedance of the second transformer.

When an auto-transformer is used, the relative currents supplied by each transformer are determined by the ratio of the two sections of the auto-transformer. The auto-transformer adds a voltage to the voltage drop in the transformer with the lower impedances and subtracts a voltage from the voltage drop in the transformer with the higher impedance. Auto-transformers for use in paralleling power transformers are specially designed for each installation. The wiring diagram showing the method of connecting the auto-transformer is usually furnished.

In general, transformers built to the same manufacturing specifications as indicated by the nameplate may be operated in parallel.

Connecting transformers in parallel when the low voltage tension is comparatively low requires care that the corresponding connecting bars or conductors have approximately the same impedance. If they do not, the currents will not divide properly.

Information Courtesy of ABB Power Transformers

FACTORY FIELD TEST OF POWER TRANSFORMER BASIC INFORMATION


There are a number of field tests that are considered good predictive maintenance practices and these should be performed periodically to spot trouble. These tests are also useful for diagnosing transformer trouble.

A Megger test consists of applying a high DC voltage, usually 1000 V, to each winding with the other windings grounded and to all windings connected in parallel. The Megger readings are in megohms and these must be temperature corrected for meaningful results.

The megger readings should be compared to earlier test results to detect any downward trend in resistance values. The voltage produced by a megger is high enough to cause insulation breakdown if there are gross faults, but is really not sensitive enough to detect minor problems in transformers in the higher voltage classes.

A Doble test is somewhat more sensitive than the Megger test. An AC voltage, up to 10 kV, is applied to the winding insulation and leakage current is measured. In addition to the leakage current, the power factor of the insulation is computed.

A high power factor indicates lossy insulation, which can mean imminent trouble. In addition to the winding insulation, the Doble test is used to measure the power factor of bushing insulation. When testing condenser type bushings, the capacitance tap is utilized.

The Doble test set is also used to measure the excitation current through the winding by applying an AC voltage across the winding. High power factor readings during this test can indicate flaws in the turn-to-turn insulation.

A TTR test can be used as a diagnostic test in the field. Always connect the TTR test set clamp leads to a secondary winding of the transformer under test. Connect the TTR test set clip leads to the primary winding that is on the same core leg as the secondary winding being tested, observing that the polarity of the red clip test lead matches the polarity of the red clamp test lead.

Set the ratio dials just above zero and give the generator wheel a half turn. The galvanometer should deflect to the left, indicating the ratio dials need to be raised. A deflection to the right means that the polarity of the test leads is incorrect.

This can be corrected by swapping the two clip test leads. After the correct polarity has been verified, slowly turn the generator and make the appropriate adjustments to the ratio dials in order to keep the galvanometer needle centered (zero current in the clip test leads). When the ratio dials are almost set to the right ratio, the generator can be cranked faster to get the proper voltage indication on the voltmeter (8 V).

If the voltmeter reads low voltage with the ammeter reading high current, this is usually an indication of shorted turns, either in the primary or in the secondary. A zero deflection on the galvanometer at every ratio settings indicates an open primary winding because no current can flow in the clip
test leads.

If the galvanometer deflection is always to the right and cannot be corrected by reversing the test leads, then this may indicate an open secondary winding and voltage cannot be generated in the primary winding.