DISTRIBUTION TRANSFORMER TYPES BASIC AND TUTORIALS


Distribution transformers may be installed on poles, on the ground on pads, and under the ground directly or in manholes and vaults. The transformers used in these types of installations differ mainly in their packaging, as the internal operating features are very much the same.

Overhead Transformers
The overhead type of distribution transformer is mounted directly on a pole by means of two lugs, welded to the transformer tank, that engage two bolts on the pole, as shown in Figure 11-2a; this is known as direct mounting, in contrast to older methods in which the transformer was bolted to a pair of hanger irons that were hung over a cross arm.


Figure 11-2a. Direct pole mounting of a transformer (Courtesy Westinghouse Electric Co.)


Where more than one transformer is required, as in power banks, the transformer lugs engage studs on a bracket which is bolted, like a collar, around the pole; the units form a cluster around the pole, from which the term cluster mounting is derived; see Figure 11-2b.


Figure 11-2b. Cluster mounting of transformers. (Courtesy Long Island Lighting Co.)


Where the load (weight) of the transformer or transformers may be too great for the pole, they may be placed on a platform erected between two or more poles in a structure, or they may be placed on a protected ground-level pad.

Pad-Mounted Transformers
Transformers may be mounted on concrete pads at, or slightly below, ground level within an enclosure or compartment that may be locked for protection. These are generally installed as part of so-called underground residential distribution (URD) systems.

The transformers may have their energized terminals exposed when the compartment is open, or the terminals may be mounted behind an insulating barrier and connections from the cables made through bayonet-type connections on insulated elbows which are plugged into jacks connected to the terminals; these units are referred to as dead-front units and provide an additional margin of safety.

Underground Transformers
In the underground type of transformer, also called the subway type, the tank is not only hermetically sealed for water tightness, but its walls, bottom, and cover are made thicker to withstand higher internal and external pressures; the cover is bolted to the tank (with intervening gaskets) by a relatively large number of bolts, and in some instances, welding is used. These units are designed to operate completely submerged in water.

In larger units, where cooling of the tank itself is not sufficient, radiator fins are welded to the tank to provide additional cooling surface, or pipes are welded to the tank for the circulation of oil through them; in the latter case, the additional surface of the pipes as well as the circulating oil is useful for cooling.

Connections to the supply cables are made by means of watertight wiped joints between a fluid-tight bushing and the cable sheath. Another means provides for the making of connections in a chamber attached to the transformer tank in which the primary-voltage transformer windings are brought out in fluid-tight bushings.

In some units, this chamber also houses high-voltage disconnecting and grounding switches. Where these units supply low-voltage secondary networks, they also house the network protector in another watertight compartment, usually situated at the opposite end of the transformer tank from the primary connection and switch chamber.

BOOSTER TRANSFORMERS CONNECTION & OPERATION BASIC AND TUTORIALS


Ordinary distributing transformers applied as illustrated (Fig. 1) are used when it is necessary to raise, by a fixed percentage, the voltage delivered by a line, as it is when transformer ratios do not give quite the right voltage or when line drop is excessive.

Fig. 1 Boosting transformers.

A booster raises the voltage of any primary circuit in which it may be inserted by the amount of the secondary voltage of the booster (see Fig.1).

EXAMPLE
On a long single-phase 2080-V lighting branch so heavily loaded that the pressure drops more than the amount for which the normal regulation of the feeder will compensate, a 110-V transformer inserted in the line as a booster will raise the pressure of the primary branch on the load side of the booster by 110 V.

This raises the secondary pressure 5.5 percent on all the transformers beyond the booster. With 440-V service supplied by star-connected 230-V transformers, a 10 percent booster in each phase raises the normal pressure of 230/400 V to 253/440 V.

The connections for a simple booster are shown in Fig. 1, I, the line pressure being raised from 2080 to 2184 V, or 5 percent. The connection at II is that for an augmented booster in which the line pressure is raised from 2080 to 2190 V, because the primary of the booster is connected across the line on the far side and the booster is boosted as well as the line.

This gives an increase of 5.5 percent in the line pressure. Figure 1, II, shows a 10 percent simple booster and IV an augmented 11.1 percent booster.

The transformers shown in Fig.1 have a 10:1 or 20:1 ratio, and the percentages shown apply only to transformers of this ratio. If boosters having a ratio of 2080 to 115/230 are used, the percentages are increased by about 10 percent. Figure 1, I, would then become 5.5 percent; II, 6.05 percent; III, 11.1 percent; and IV, 12.2 percent.

Previous Articles