DELTA, STAR, AND OPEN DELTA TRANSFORMER CONNECTION COMPARISON


The choice between the methods would be governed largely by the service requirements. When the three transformers are delta-connected, one can be removed without interrupting the performance of the circuit, the two remaining transformers in a manner acting in series to carry the load of the missing transformer.

The desire to obtain immunity from a shutdown due to the disabling of one transformer has led to the extensive use of the delta connection of transformers, especially on the low-potential delivery side. It is to be noted that if one transformer is crippled, the other two will be subjected to greatly increased losses.

Thus, if three delta-connected transformers are equally loaded until each carries 100 A, there will be 173 A in each external circuit wire. If one transformer is now removed and 173 A continues to be supplied to each external circuit wire, each of the remaining transformers must carry 173 A, since it is now in series with an external circuit.

Therefore, each transformer must now show 3 times as much copper loss as when all three transformers were active, or the total copper loss is now increased to a value of 6 relative to its former value of 3. An open-delta installation is made frequently when considerable future increase in load is expected.

The increase can be accommodated by adding the third transformer to the bank at a later date and thus increasing the capacity of the load that can be carried by about 75 percent.

A change from delta to Y in the secondary circuit alters the ratio of the transmission emf to the receiver emf from 1 to 1.73 .

On account of this fact, when the emf of the transmission circuit is so high that the successful insulation of transformer coils becomes of constructive and pecuniary importance, the three-phase line sides of the transformers are connected in “star” and the neutral is grounded.

The windings of most transformers operating on systems of 100,000 V or more are star-connected.


Comparative cost of transformers for different grouping for three-phase service. 
The accompanying table shows the costs of the single-phase transformers, of proper capacities for either a delta or an open-delta grouping, and of a three-phase transformer to serve a 75-kVA installation. The relative costs will be the same for the present date.


CONSTANT CURRENT TRANSFORMER BASIC OPERATION TUTORIALS


The operation of low-voltage lamps in parallel on a constant-voltage system necessitates a prohibitive expenditure for conducting material when the area to be lighted is extensive and the lamps are widely separated. For such service it is the common practice to operate the lamps, which are connected in series, with a constant current.

The constant-current transformer is a special form of transformer which converts alternating current at a constant voltage to a constant (alternating) current with a voltage varying with the load. It consists of a primary coil upon which the constant voltage is impressed, a secondary coil (or coils) movable with respect to the primary, and a core of low magnetic reluctance.

It depends for its regulation upon the magnetic leakage between the primary and secondary coils. Consider first the primary coil; with the constant emf impressed upon this coil the total magnetism within the coil will be practically constant under all conditions.

The emf generated in the secondary will depend upon the strength of the field which it surrounds. In all types of stationary transformers the secondary current is opposite in general time direction to the primary, so that there is not only a repulsive thrust between the two coils but also a considerable tendency for the magnetic lines from the primary to be forced out into space without penetrating the secondary.

In the ordinary constant-voltage transformer the repelling action between the two currents is prevented from producing motion of the coils by the rigid mechanical construction, while the proximity of the primary and secondary coils limits the magnetic leakage.

In the constant-current transformer, however, the repelling action is utilized to adjust the relative positions of the primary and secondary coils; when the coils are widely separated, the paths for the leakage lines are increased and the lines which the secondary surrounds are fewer than when the coils are quite close together.

The counterweights mechanically attached to the movable coil (or coils) are so arranged that when the desired current exists in the secondary coil (independent of its position along the core), the weights are just balanced. An increase in the current increases the repulsion and causes the coils to separate.

With any current less than normal, the repelling force diminishes, and the primary and secondary coils approach each other, thereby restoring the current to normal. The primary can be wound for any reasonable voltage (say, as high as 10,000 V), while the secondary can be wound for the voltage required for operating the number of lamps in the circuit—from 15 to 200 or more lamps.

Previous Articles