WYE WYE CLOSED TRANSFORMER BANKING

YY CLOSED/ NEUTRAL = PRIMARY YES SECONDARY YES
How To Bank YY Close Transformers?


WHERE USED
To supply single- and three-phase loads on four-wire, multi-grounded systems. When a system has changed from delta to a four-wire wye in order to increase system capacity, existing transformers may be used (Example: Old system was 2400 volts delta; new system is 2400/4160Y volts. Existing 2400/4160Y-volt transformers may be connected in wye and used.)


YY FOR LIGHTING AND POWER
This diagram shows a system on which the primary voltage was increased from 2400 volts to 4160 volts to increase the potential capacity of the system. The previously delta-connected distribution transformers are now connected from line to neutral.

The secondaries are connected in Y. In this system, the primary neutral is connected to the neutral of the supply voltage through a metallic conductor and carried with the phase conductor to minimize telephone interference.

If the neutral of the transformer is isolated from the system neutral, an unstable condition results at the transformer neutral caused primarily by third harmonic voltages. If the transformer neutral is connected to ground, the possibility of telephone interference is greatly enhanced, and there is also a possibility of resonance between the line capacitance to ground and the magnetizing impedance of the transformer.

Dotted lines indicate transformer tanks are grounded.



CAUTION
The primary neutral should be tied firmly to the system neutral; otherwise, excessive voltages may develop on the secondary side. (5)

It is necessary that the primary neutral be available when this connection is used, and the neutrals of the primary system and of the bank are tied together as shown. If the three-phase load is unbalanced, part of the load current flows in the primary neutral.

The third-harmonic component of the transformer exciting current also flows in the primary neutral. For these reasons, it is necessary that the neutrals be tied together as shown. If this tie were omitted, the line to neutral voltages on the secondary would be very unstable.

That is, if the load on one phase were heavier than on the other two, phases would rise. Also, large third-harmonic voltages would appear between lines and neutral, both in the transformers and in the secondary system, in addition to the 60-Hz component of voltage.

This means that for a given value of RMS voltage, the peak voltage would be much higher than for a pure 60-Hz voltage. This overstresses the insulation both in the transformers and in all apparatus connected to the secondaries.


IMPEDANCE & GROUNDING
The wye-grounded/wye-grounded connection should be used only on a grounded system. It will pass ground-fault current from the primary system. Single and three-phase loads may be connected depending on the rating of the individual units, it is not necessary that the impedance of each unit in the bank be the same.



TRANSFORMER NO LOAD LOSSES BASICS AND TUTORIALS

TRANSFORMER NO LOAD LOSSES BASIC INFORMATION
What Are The Transformer No Load Losses?


Alternating magnetic flux produces both hysteresis losses and eddy-current losses in the steel. As we have seen, hysteresis losses depend on several factors including the frequency, the peak flux density, the type of core steel used, and the orientation of the flux with respect to the ‘‘grain’’ of the steel.

All of the above factors, except the frequency, are under the control of the transformer designer. Core losses are sometimes referred to as iron losses and are commonly referred to as no load losses, because core losses do not require load currents.

Decreasing the induced voltage per turn can reduce the peak flux density. This obviously involves increasing the numbers of turns in both the primary and secondary windings in order to maintain the same transformer turns ratio.

The disadvantage of adding more turns is that this increases the length of conductor and increases the conductor resistance. More cross sectional area is required in order to keep the resistance constant.

Doubling the number of turns requires about four times the volume of copper. Another way of reducing core losses is to use various types of low-loss core steels that are now available, including ‘‘amorphous’’ core materials, which have extremely low losses and superior magnetic properties.

Unfortunately, amorphous core materials have ceramic-like properties, so fabricating transformer cores with these materials is much more difficult than with laminated steel cores.

With grain-oriented steel, the direction of the core flux must be kept more or less parallel to the grain of the steel by mitering the corners of the laminations where the flux changes direction by 90°. Since the flux will cross the grain at about a 45° angle at the mitered edges, the hysteresis losses will increase somewhat in these places.

These additional localized core losses must be factored into the calculation of the total core losses. Building up the core with thin laminated strips controls eddy losses in the core, each strip having an oxide film applied to the surface.

The oxide film is extremely thin and it is more like a high-resistance film than true electrical insulation; but since the potential differences between adjacent laminations is quite small, the resistance of the oxide film is very effective in breaking up the eddy current paths.

During the manufacture of the core, the core cutting machine must not be allowed to get dull; otherwise, ‘‘burrs’’ will form along the edges of the laminations. Burrs are imperfections that form electrical bridges between the laminations and create paths for eddy currents and increased losses.

Sometimes the eddy currents near a burr can be large enough to cause localized overheating that can actually cause core damage. Core losses are approximately proportional to the square of the excitation voltage E applied to the transformer.

Therefore, placing an equivalent linear conductance Gm across the transformer terminals can approximate transformer core losses. The core losses are expressed by Wm = E^2Gm

Previous Articles