25 KVA DISTRIBUTION TRANSFORMER SPECIFICATION SAMPLE TUTORIALS

25 KVA DISTRIBUTION TRANSFORMER SPECIFICATION SAMPLE
Specification Sample of 25 KVA Distribution Transformer


Pole Mounted Amorphous Transformer Specification

Brand:
Rating: 25 kVA, Single Phase
Primary Voltage: 7620/13,200V-Y
Secondary Voltage: 120/240 Volts
BIL: 95kV
Frequency: 60 hz
Cooling Class: ONAN
Temperature Rise: 65 deg. Centigrade
No Load Loss: at most 72 watts
Load Loss: at most 411 watts
Tap Changer: +/- 2 - 2.5% above and below nominal voltage The tap changer switch shall be an externally operated
through a rotating switch.Externally accessible.
Conductor: All Aluminum conductor
Core: Amorphous Alloy
Insulation: Oil Immersed (Mineral)
Primary Connection: Eye Bolt Clamp or Plug Type
Secondary COnnection: Eye Bolt Clamp or Plug Type
Other Features: (1) Double Bushing on the Primary side, H1 & H2
(2) Secondary Bushing shall be X1,X2,X3 configuration
(3) Polarity: Additive
(4) Lifting Lugs
(5) Support Lugs
(6) Collor: Gray



TESTED & BUILT IN ACCORDANCE WITH ALL APPLICABLE ANSI STANDARDS

69 kV VOLTAGE TRANSFORMER SPECIFICATION EXAMPLE TUTORIALS

69 kV VOLTAGE TRANSFORMER SPECIFICATION EXAMPLE 
Specification Example of 69 kV Voltage Transformer


VOLTAGE TRANSFORMER

Brand:
Rated Voltage (kV): 72.5kV
Rated Frequency (Hz): 60
Type:         EMFC 84
Design:         Outdoor
Basic Insulation Level (kV) : 350kV
Rated primary voltage and ratio 69,000 Grd Y/40,250
Ratio: 350/600 & 350/600:1
Accuracy Class at Standard Burden: 0.3
Thermal Burden Rating: 200 VA @ 300 ambient