BUCHHOLZ RELAY OR POWER TRANSFORMER BASICS AND TUTORIALS

BUCHHOLZ RELAY FOR POWER TRANSFORMER BASIC INFORMATION

What Are Buchholz Relay? How Buccholz Relay Works?


The Buchholz Relay (Gas Relay) is designed to protect equipments submerged in insulating liquid, by means of supervision of the oil abse nce or abnormal flow, and abnormal gassing caused by the equipment. Buchholz relay is usually fitted on transformers provided with an expansion tank for the insulating liquid.

Buchholz Relay
Buchholz relay is capable to accurately detect, for example, the following problems: Leakage of insulating liquid, short - circuit inside the equipment causing a great displacement of insulating liquid, inside gassing due to intermittent or continuous failures occurring inside the equipment.

Buchholz relay is usually installed between the main tank and the oil expansion tank of the transformer.

Buchholz relay housing is made of cast iron, having two flanged openings and two sight glasses showing a graduated scale of gas volume. There are two inside floats, being that the upper float is fo rced to move downwards (this also happens in case of oil leakage).

On the other hand, in case an excessive gassing causes an oil ci rculation through the relay, the lower float reacts, even before the gas reaches the relay. In both cases, the floats make contacts when they are displaced.

The Buchholz Relay has a device for the inside float testing and locking. To check for proper operation of the relay contacts, when it is installed in the transformer, proceed as follows:

Alarm:
· Connect an Ohmmeter to terminal s + C - D. It should indicate an open circuit.

· Remove the testing device plug and introduce it upside down into the device, lowering it as much as possible in all of its length. The Ohmmeter should indicate a closed circuit.

Shutdown
· Connect an Ohmmeter to terminals + A - B. It should indicate an open circuit.

· Remove the testing device plug and introduce it upside down into the device, lowering it as much as possible in all of its length. The Ohmmeter should indicate a closed circuit.

Before supplying po wer to the transformer, the following items should be checked:

· Remove the lid of the relay -testing device.

· Remove the float -locking pin from the inside of the testing device. Both floats should be free to move.

· Replace the cover of the relay -testing device.

· Purge the air from the relay by means of the 1/8” air valve located on the relay lid.

· Check the relay for possible leakage that might have occurred during the installation on the transformer and fix it.

· Check the relay for proper fitting wi th regards to the oil float direction, which arrow should be pointing towards the transformer’s oil expansion tank.

If the alarm sounds without turning off the transformer, it is necessary to turn it off immediately and then test the gas removed from the inside of the relay. In this case, the origin of the failure can be assessed according to the gas testing result, i.e.:

· Combustible gas (contents of acetylene): In this case there must be a failure to be repaired on the electrical part;

· Non-combustible gas (without acetylene) : in this case, it means there is pure air. The transformer can be turned on again without danger after the air is bled out from the relay. When the alarm sounds repeatedly, it indicates that air is penetrating into the transformer. Tur n it off and repair the failure.

· No gassing (the gas level inside the relay is getting lower and an amount of air is being drawn through the open valve), in this case, the oil level is too low, possibly due to a leakage. Top up with oil until the control level and carry out the air tightness essay.

The transformer is turned off without a previous alarm. In this case, the transformer must have been thermally overloaded. Turn it on again after a considerable time interval for cooling. The failure can be found atcthe short-circuit contact in the protection relay system.

The alarm sounds and the transformer is shutdown immediately before or after the alarm sounds. In this case, one of the above mentioned failures must be the cause. Make the gas testing and proceed as described above.


ATTENTION!
Float locking device for transport purpose and testing of contacts : After installing the relay, remove the insert used to lock the floats.

Operation: To test the contacts, press the internal part with the lid pin. The contacts should actuate automatically. If everything is properly working, close the device again in order to prevent any leakage. Now the relay is ready to be put in operation.


NOTE: The insert is used for transport purposes only.

THE SCOTT TRANSFORMER CONNECTION BASIC AND TUTORIALS

THE SCOTT TRANSFORMER CONNECTION BASIC INFORMATION
What Is Scott Transformer Connection? how Scott Transformer Connection Works?


In order to overcome the disadvantage of the T connection, the Scott connection uses two single-phase transformers of a special design to transform three phase voltages and currents into two-phase voltages and currents.

The first transformer, called the ‘‘main,’’ has a center-tapped primary winding connected to the three-phase circuit with the secondary winding connected to the two-phase circuit. It is vital that the two halves of the center-tapped primary winding are wound around the same core leg so that the ampere-turns of the two halves cancel out each other. The ends of the center-tapped main primary winding are connected to two of the phases of the three-phase circuit.


The second transformer, called the ‘‘teaser,’’ has one end of its primary winding connected to the third phase of the three-phase circuit and the other end connected to the center tap of the primary winding of the main. The Scott connection requires no primary neutral connection, so zero-sequence currents are blocked.

The secondary windings of both the main and teaser transformers are connected to the two-phase circuit. The Scott connection is shown in Figure 2.18 for a two-phase, five-wire circuit, where both secondary windings are center-tapped and the center taps are connected to the neutral of the five wire circuit. Three-wire and four-wire configurations are also possible.



If the main transformer has a turns ratio of 1: 1, then the teaser transformer requires a turns ratio of 0.866:1 for balanced operation. The principle of operation of the Scott connection can be most easily seen by first applying a current to the teaser secondary windings, and then applying a current to the main secondary winding, calculating the primary currents separately and superimposing the results.

Apply a 1.0 per unit load connected between phase 1 and phase 3 of the secondary:


Secondary current from the teaser winding into phase 1 1.0∠90°
Secondary current from the teaser winding into phase 3 1.0∠90°
Primary current from A phase into the teaser winding 1.1547∠90°
Primary current from B phase into the main winding 0.5774∠90°
Primary current from C phase into the main winding 0.5774∠90°

The reason that the primary current from A phase into the teaser winding is 1.1547 per unit is due to 0.866:1 turns ratio of the teaser, transforming 1/0.866 1.1547 times the secondary current. This current must split in half at the center tap of the main primary winding because both halves of the main primary winding are wound on the same core and the total ampere-turns of the main winding must equal zero.

Apply a 1.0 per unit load connected between phase 2 and phase 4 of the secondary:

Secondary current from the main winding into phase 2 1.0∠0°
Secondary current from the main winding into phase 4 1.0∠0°
Primary current from B phase into the main winding 1.0∠0°
Primary current from C phase into the main winding 1.0∠0°
Primary current from A phase into the teaser winding 0

Superimpose the two sets of primary currents:

I a 1.1547∠90° 0 1.1547∠90°
I b 0.5774∠90° 1.0∠0° 1.1547∠ 30°
I c 0.5774∠90° 1.0∠0° 1.1547∠210°

Notice that the primary three-phase currents are balanced; i.e., the phase currents have the same magnitude and their phase angles are 120° apart. The apparent power supplied by the main transformer is greater than the apparent power supplied by the teaser transformer.

This is easily verified by observing that the primary currents in both transformers have the same magnitude; however, the primary voltage of the teaser transformer is only 86.6% as great as the primary voltage of the main transformer.

Therefore, the teaser transforms only 86.6% of the apparent power transformed by the main. We also observe that while the total real power delivered to the two phase load is equal to the total real power supplied from the three-phase system, the total apparent power transformed by both transformers is greater than the total apparent power delivered to the two-phase load.

Using the numerical example above, the total load is 2.0 per unit. The apparent power transformed by the teaser is 0.866 I a 1.0 per unit, and the apparent power transformed by the main is 1.0 I b 1.1547 per unit for a total of 2.1547 per unit of apparent power transformed.

The additional 0.1547 per unit of apparent power is due to parasitic reactive power flowing between the two halves of the primary winding in the main transformer. Single-phase transformers used in the Scott connection are specialty items that are virtually impossible to buy ‘‘off the shelf ’’ nowadays.



Previous Articles