The tertiary winding of an autotransformer,
or three-winding transformer, is usually of much smaller kVA rating than the
main windings. Therefore, fuses or overcurrent relays set to protect the main
windings offer almost no protection to tertiaries.
During external system ground faults,
tertiary windings may carry very heavy currents. Hence, to guard against
failure of the primary protection for external ground faults, separate tertiary
overcurrent protection may be desirable.
The method selected for protecting the
tertiary generally depends on whether or not the tertiary is used to carry
load. If the tertiary does not carry load, protection can be provided by a
single overcurrent relay connected to a CT in series with one winding of the Δ.
This relay will sense system grounds as
well as phase faults in the tertiary or in its leads. When tertiary windings
are connected by cables, the overcurrent protection provided to the tertiary
winding should account for the thermal withstand of the cables.
Alarming and tripping as a result of a
prolonged unbalance condition or load tap changer malfunction should prevent
damage to cables. If the tertiary is used to carry load, partial protection can
be provided by a single overcurrent relay supplied by three CTs, one in each
winding of the Δ and connected in parallel to the relay.
This connection provides only zero sequence
overload protection and does not protect for positive and negative sequence
overload current. In this case, the relay will operate for system ground but
will not operate for phase faults in the tertiary or its leads.
Where deemed necessary, separate relaying
such as differential type should be provided for protection for phase faults in
the tertiary or its leads. The setting of the tertiary overcurrent relay can
normally be based on considerations similar to those in line time overcurrent.